Figure 4-3. Problems with communications flowchart
Communications established but have “Block_err” or an
“Alarm” Condition.
See
“PlantWeb™ alerts” on page 145
Read the following parameters in the Resource Block to
determine the recommended action.
BLOCK_ERR (see
SUMMARY_STATUS (see
DETAILED_STATUS (see
)
Problem Identified?
Yes
No
Perform Recommended
Action, see
For more detailed
information
Perform the following steps in the Sensor Transducer Block
to determine the recommended action.
BLOCK_ERR (see
)
XD_ERR (see
RECOMMENDED_ACTION (see
)
SENSOR_DETAILED STATUS (see
)
If error condition does not exist in
the Resource Block then it is a
configuration problem, see
Problem Identified?
Yes
No
If the problem persists
contact your local Emerson
representative.
Problem Identified?
Perform Recommended
Action, see
Yes
No
Perform Recommended
Action, see
.
Yes
No
Perform Recommended
Action, see
Problem Identified?
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......