151
Reference Manual
00809-0100-4021, Rev GC
Section 4: F
OUNDATION
fieldbus Configuration
April 2014
Foundation™ fieldbus configuration
4.6.1
Sensor transducer block diagnostics
lists the potential errors and the possible corrective actions for the given values. The
corrective actions are in order of increasing system level compromises. The first step should
always be to reset the transmitter and then if the error persists, try the steps in
. Start with
the first corrective action and then try the second.
Table 4-5. Sensor Transducer Block BLOCK_ERR messages
Condition name and description
Other
Out of Service: The actual mode is out of service
Table 4-6. Sensor Transducer Block XD_ERR messages
Condition name and description
Electronics Failure: An electrical component failed
I/O Failure: An I/O failure occurred
Software Error: The software has detected an internal error
Calibration Error: An error occurred during calibration of the device
Algorithm Error: The algorithm used in the transducer block produced an error due to overflow, data
reasonableness failure, etc.
Table 4-7. Sensor Transducer Block STB.SENSOR_DETAILED_ STATUS messages
STB.SENSOR_DETAILED_STATUS
Description
Invalid Configuration
Wrong sensor connection with wrong sensor type
ASIC RCV Error
The micro detected a chksum or start/stop bit failure with
ASIC communication
ASIC TX Error
The ASIC detected a communication error
ASIC Interrupt Error
ASIC interrupts are too fast or slow
Reference Error
Reference resistors are greater than 25% of known value
ASIC Configuration Error
ASIC registers were not written correctly. (Also
CALIBRATION_ERR)
Drift Alert
Difference between sensor values has exceeded user specified
limit
Hot Backup Active
The device is currently operating in Hot Backup mode,
meaning the primary sensor has failed
Sensor Open
Open sensor detected
Sensor Shorted
Shorted sensor detected
Terminal (Body) Temperature Failure
Open or shorted PRT detected
Sensor Out of Operating Range
Sensor readings have gone beyond PRIMARY_VALUE_RANGE
values
Sensor beyond operating limits
Sensor readings have gone below 2% of lower range or above
6% of upper range of sensor
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......