Section 3: HART commissioning
April 2014
3.10.2
Master reset
Master Reset
resets the electronics without actually powering down the unit. It does not return
the transmitter to the original factory configuration.
3.10.3
Intermittent sensor detect
The following steps indicate how to turn the Intermittent Sensor Detect (also knows as Transient
Filter) feature
ON
or
OFF
. W
hen the transmitter is connected to a Field Communicator, use the
fast key sequence and choose
ON
(normal setting) or
OFF
.
3.10.4
Intermittent threshold
The threshold value can be changed from the default value of 0.2%. Turning the Intermittent
Sensor Detect feature
OFF
or leaving it
ON
and increasing the threshold value above the default
does not affect the time needed for the transmitter to output the correct alarm signal after
detecting a true open sensor condition. However, the transmitter may briefly output a false
temperature reading for up to one update in either direction (see
) up to
the threshold value (100% of sensor limits if Intermittent Sensor Detect is
OFF
). Unless a rapid
response rate is necessary, the suggested setting is
ON
with 0.2% threshold
.
Figure 3-8. Open Sensor Response
HART 5 Fast Keys
2, 2, 7, 6
HART 7 Fast Keys
2, 2, 7, 6
HART 5 Fast Keys
2, 2, 7, 5, 2
HART 7 Fast Keys
2, 2, 7, 5, 2
HART 5 Fast Keys
2, 2, 7, 5
HART 7 Fast Keys
2, 2, 7, 5
0
0
5
10
15
20
25
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Tr
ansmitt
e
r O
u
tput (mA
)
Time (seconds)
When Intermittent Sensor Detect is
OFF, a false temperature output is
possible when an open sensor
condition is detected. A false
temperature output in either direction
up to the threshold value (100 % of
sensor limits if Intermittent Sensor
Detect is OFF) is possible when an open
sensor condition is detected.
Normal open sensor responses
High Alarm
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......