0
Block
Errors
7.11.8
Block Errors
lists conditions reported in the BLOCK_ERR parameter. Conditions in italics
are inactive for the AI block and are given here only for your reference.
Table 7-21 BLOCK_ERR Conditions
Condition
Number
Condition Name and Description
0
Other
1
Block Configuration Error: the selected channel carries a measurement that is incompatible with
the engineering units selected in XD_SCALE, the L_TYPE parameter is not configured, or CHANNEL
= zero.
2
Link Configuration Error
3
Simulate Active: Simulation is enabled and the block is using a simulated value in its execution.
4
Local Override
5
Device Fault State Set
6
Device Needs Maintenance Soon
7
Input Failure/Process Variable has Bad Status: The hardware is bad, or a bad status is being
simulated.
8
Output Failure: The output is bad based primarily upon a bad input.
9
Memory Failure
10
Lost Static Data
11
Lost NV Data
12
Readback Check Failed
13
Device Needs Maintenance Soon
14
Power Up
15
Out of Service: The actual mode is out of service.
7.11.9
Modes
The AI Function Block supports three modes of operation as defined by the MODE_BLK
parameter:
•
Manual (Man) The block output (OUT) may be set manually.
•
Automatic (Auto) OUT reflects the analog input measurement or the simulated value
when simulation is enabled.
•
Out of Service (O/S) The block is not processed. FIELD_VAL and PV are not updated and
the OUT status is set to Bad: Out of Service. The BLOCK_ERR parameter shows Out of
Service. In this mode, you can make changes to all configurable parameters. The target
mode of a block may be restricted to one or more of the supported modes.
Summary of Contents for Rosemount OCX 8800
Page 2: ......
Page 41: ...Instruction Manual IM 106 880C OI Section 2 Installation April 2017 Section contents 17 ...
Page 205: ...Alarm Relay Events April 2017 Instruction Manual IM 106 880C OI 17 8 Alarm Relay Events ...
Page 251: ...Replace Tube Fittings April 2017 Instruction Manual IM 106 880C OI 22 4 Install Tube Fittings ...
Page 261: ...Instruction Manual IM 106 880C OI Safety Data April 2017 Appendix contents 233 ...
Page 263: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 235 ...
Page 267: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 239 ...
Page 271: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 243 ...
Page 273: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 245 ...
Page 275: ...Instruction Manual Safety Data IM 106 880C OI April 2017 IMPORTANT Safety Instructions 247 ...
Page 277: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 249 ...
Page 279: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 251 ...
Page 300: ...Instruction Manual IM 106 880C OI Index April 2017 Manual index 27 4 ...
Page 304: ...Index April 2017 Instruction Manual IM 106 880C OI 27 8 Manual index ...
Page 305: ......