1
Introduction
To comply with local standards and jurisdictional authorities, perform end-to-end loop
testing of fire protection alarm systems, including detectors, periodically. Many safety
authorities and plant managers of high value/high risk assets and facilities insist on
quarterly end-to-end testing of their entire fire protection systems using an external flame
simulator.
Rosemount Flame Simulators emit electromagnetic radiation in a unique sequential
pattern corresponding to and recognizable as fire by the specific Rosemount 975 Flame
Detector. This allows the detector to be tested under real fire conditions without the
associated risk of an open flame.
Rosemount Flame Simulators are ATEX certified EExd for use in Zone 1, Zone 2, Zone 21,
and Zone 22 hazardous areas and are powered by rechargeable lithium ion batteries.
When fully charged, the Flame Simulator will operate for at least 1,000 tests without
recharging.
The Rosemount Flame Simulator is the only non-hazardous and safe method to test the
flame detector's sensors, internal electronics, alarm activation software, cleanliness of the
viewing window/lens, wiring integrity, actual relay activation, and proper functionality of
any other outputs used (mA, RS-485, or HART
®
).
1.1
Flame simulator compatibility with flame
detector models
The Rosemount FS-HR-975 Flame Simulator is compatible with the following:
Table 1-1: Flame simulator compatibility
Simulator
Part number
Compatible with
Multi-spectrum infrared hydrogen flame
simulator
FS-HR-975
Rosemount 975HR
1.2
Features and benefits
•
Used for maintenance and testing of flame detectors.
•
Can activate the flame detector from a distance of 39.4 ft (12 m).
•
Includes rechargeable battery.
•
Operates at least 1,000 tests before the battery must be recharged.
1.3
Principles of operation
The Rosemount FS-HR-975 emits infrared energy, which is filtered to emit
electromagnetic radiation in unique sequential patterns, corresponding to and
recognizable as fire by the Rosemount 975HR Flame Detector.
Reference Manual
Introduction
00809-0900-4975
May 2022
Rosemount FS-HR-975
7
Summary of Contents for Rosemount FS-HR-975
Page 1: ...Reference Manual 00809 0900 4975 Rev DD May 2022 Rosemount FS HR 975 Flame Simulator ...
Page 4: ...4 ...
Page 6: ...Contents Reference Manual May 2022 00809 0900 4975 6 Emerson com Rosemount ...
Page 14: ...Operation Reference Manual May 2022 00809 0900 4975 14 Emerson com Rosemount ...
Page 18: ...Maintenance Reference Manual May 2022 00809 0900 4975 18 Emerson com Rosemount ...
Page 20: ...Ordering information Reference Manual May 2022 00809 0900 4975 20 Emerson com Rosemount ...
Page 26: ...Product certifications Reference Manual May 2022 00809 0900 4975 26 Emerson com Rosemount ...