d. Setting the interval timer parameters.
2. Simulating an alarm means making the transmitter energize or de-energize an
alarm relay.
5.4.2
Definitions
Assigning
alarms
There are four alarm relays. The relays are freely assignable to any sensor
and to either the measurement (for example, chlorine) or temperature.
Alarm relays can also be assigned to operate as interval timers or as fault
alarms. A fault alarm activates when the transmitter detects a fault in
either itself of the sensor.
Fault alarm
A fault condition exists when the transmitter detects a problem with the
sensor or with the transmitter itself that is likely to cause seriously
erroneous readings. If an alarm was programmed as a fault alarm, the
alarm activates. At the same time, a fault message appears in the main
display.
Alarm logic,
setpoints,
and
deadbands
See
.
Figure 5-1: High Alarm Logic
A. Chlorine, ppm
B. Alarm activates
C. Deadband = 0.3 ppm
D. Alarm deactivates
E. Time
F. High alarm setpoint
The alarm activates when the chlorine concentration
exceeds the high setpoint. The alarm remains
activated until the reading drops below the value
determined by the deadband.
Reference Manual
Programming the transmitter
00809-0100-3412
May 2019
Rosemount FCL 1056
47
Summary of Contents for Rosemount FCL
Page 4: ...4 ...
Page 18: ...Install Reference Manual May 2019 00809 0100 3412 18 Emerson com Rosemount ...
Page 26: ...Wire Reference Manual May 2019 00809 0100 3412 26 Emerson com Rosemount ...
Page 27: ...Reference Manual Wire 00809 0100 3412 May 2019 Rosemount FCL 1056 27 ...
Page 28: ...Wire Reference Manual May 2019 00809 0100 3412 28 Emerson com Rosemount ...
Page 76: ...Digital communications Reference Manual May 2019 00809 0100 3412 76 Emerson com Rosemount ...
Page 107: ...Reference Manual 00809 0100 3412 May 2019 Rosemount FCL 1056 107 ...