D
Alert message mapping
This appendix outlines the most important alerts in the HART
®
command 48 Additional
Status field for the Rosemount
®
928. The information in this section can be used by
DeltaV
™
for alert monitoring and in the Wireless Gateway for Additional Status mapping in
Modbus
®
, OPC, and other communication protocols. A complete list of Additional Status
bits is available in the wireless gateway.
contains the device variable and variable mapping indexes for the
transmitter.
contains the most important alert messages that may be displayed in the
AMS Device Manager and Field Communication together with the location of the alert in
the HART command 48 Additional Status field.
To view active alerts in Field Communicator or AMS Device Manager, from the
Home
screen, go to
Service Tools
→
Active Alerts
.
D.1
Variable mapping
Table D-1: Device Variable Index
Device variable
Index
0
Supply voltage
1
Electronics temperature
2
Gas concentration
3
Sensor temperature
Table D-2: Device Variable Mapping Index (Cannot be Modified)
Variables
Index
PV
Gas concentration
SV
Sensor module temperature
TV
Electronics temperature
QV
Supply voltage
D.2
Alert mapping
Table D-3: Failure Alerts (F)
Message
Description
Electronics Failure
Byte 8 :: Bit 6
A failure has been detected in
the device memory,
electronics, or both.
Reference Manual
Alert message mapping
00809-0100-4928
September 2019
Rosemount 928
201
Summary of Contents for Rosemount 928
Page 1: ...Reference Manual 00809 0100 4928 Rev AE September 2019 Rosemount 928 Wireless Gas Monitor ...
Page 4: ...4 ...
Page 8: ...Contents Reference Manual September 2019 00809 0100 4928 viii Emerson com Rosemount ...
Page 106: ...Configuration Reference Manual September 2019 00809 0100 4928 106 Emerson com Rosemount ...
Page 178: ...Troubleshooting Reference Manual September 2019 00809 0100 4928 178 Emerson com Rosemount ...