193
March 2016
Reference Manual
00809-0300-4750, Rev CA
B.1 European Directive Information
.
B.1.1 Electro Magnetic Compatibility
(EMC)(2004/108/EC) and (2014/30/EU)
EN 61326-1: 2013
B.1.2 Low Voltage Directive (LVD)
(2006/95/EC) and (2014/35/EU)
EN 61010-1: 2010
B.1.3 Ingress Protection Rating for dust and
water
Degree of protection, per EN-IEC 60079-0 and EN-IEC
60529: IP66
(1)
Degree of protection, per EN-IEC 60079-0 and EN-IEC
60529: IP66, IP68 (10 m, 48 h)
(2)
Degree of protection, per EN-IEC 60079-0 and ISO 20653:
IP69K
(3)
B.1.4 European Pressure Equipment Directive
(PED) (97/23/EC) and (2014/68/EU)
PED Certification requires the “PD” option code.
CE marked models that are ordered without the “PD”
option will be marked “Not Complaint to (97/23/EC)”
Mandatory CE-marking with notified body number 0575,
for all flowtubes is located on the flowmeter label.
Category I assessed for conformity per module A
procedures.
Categories II – III assessed for conformity per module H
procedures.
QS Certificate of Assessment
EC No. 4741-2014-CE-HOU-DNV: Module H Conformity
Assessment
B.1.5 Rosemount 8750W Flanged Flowtubes
Line size 40 mm to 600 mm (1
1
/
2
- to 24-in.)
EN 1092-1 flanges and ASME B16.5 class 150 and ASME
B16.5 Class 300 flanges.
Also available in ASME B16.5 Class 600 flanges in limited
line sizes.
All other Rosemount Flanged Flowtubes – line sizes of
25 mm (1-in.) and less: Sound Engineering Practice (SEP).
Flowtubes that are SEP are outside the scope of PED and
cannot be marked for compliance with PED.
B.2 Certifications
B.2.1 Factory Mutual (FM)
Ordinary Location Certification for FM Approvals
As standard, the transmitter and flowtube have been
examined and tested to determine that the design meets
basic electrical, mechanical, and fire protection
requirements by FM Approvals, a nationally recognized
testing laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
Rosemount 8750W Magnetic Flowtube and Transmitter
Z5
All Flowtubes and Integral or Remote Mount
Transmitters (Transmitter mount codes T or R)
Non-Incendive for Class I, Division 2, Groups ABCD: T4
Dust-Ignition Proof for Class II/III, Division 1, Groups
EFG:
T5 -29 °C
≤
T
a
≤
60 °C
Enclosure Type 4X, IP66/68 (IP68 flowtube only with
Remote mount transmitter)
Install per drawing 8750W-1052
Special Condition for Safe Use (X):
1. Flowtube to be used only in a non-flammable process.
Rosemount 8750W Magnetic Flowtube and Transmitter
Z5
All Flowtubes and Wall Mount Transmitter
(Transmitter mount code W)
Non-Incendive for Class I, Division 2, Groups ABCD: T4
Dust-Ignition Proof for Class II/III, Division 1, Groups
EFG: T4
-29 °C
≤
T
a
≤
40 °C
Enclosure Type 4X, IP66/68 (IP68 flowtube only)
Install per drawing 8750W-1052
Special Condition for Safe Use (X):
1. Flowtube to be used only in a non-flammable process.
1.
The transmitter is rated IP66 when integral or remote mounted, it is
not IP68 nor IP69K rated.
2.
The IP68 rating only applies to the flowtube and the remote junction
box when the transmitter is remotely mounted. The IP68 rating is
only valid at a depth of 10 meters for 48 hours.
3.
The IP69K rating only applies to the flowtube and the remote junc-
tion box when the transmitter is remotely mounted. The tempera-
ture K = 80 °C.
Summary of Contents for Rosemount 8750W
Page 2: ......
Page 96: ...84 Reference Manual 00809 0300 4750 Rev CA Operation March 2016 Operation ...
Page 168: ...156 Reference Manual 00809 0300 4750 Rev CA Maintenance March 2016 Maintenance ...
Page 214: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 202 Wiring Diagrams ...
Page 218: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 206 Wiring Diagrams ...
Page 219: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 207 Wiring Diagrams ...
Page 220: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 208 Wiring Diagrams ...
Page 222: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 210 Wiring Diagrams ...
Page 223: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 211 Wiring Diagrams ...
Page 224: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 212 Wiring Diagrams ...
Page 225: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 213 Wiring Diagrams ...
Page 227: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 215 Wiring Diagrams ...
Page 228: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 216 Wiring Diagrams ...
Page 229: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 217 Wiring Diagrams ...
Page 263: ......