Combination coil and electrode cable
Figure 4-6:
1
2
3
19
18
17
17
A
B
C
A.
Electrode shield drain
B.
Overlapping foil shield
C.
Outer jacket
•
1 = Red
•
2 = Blue
•
3 = Drain
•
17 = Reference
•
18 = Yellow
•
19 = White
Cable preparation
Prepare the ends of the coil drive and electrode cables as shown in
. Remove only
enough insulation so that the exposed conductor fits completely under the terminal
connection. Best practice is to limit the unshielded length (D) of each conductor to less
than one inch. Excessive removal of insulation may result in an unwanted electrical short to
the transmitter housing or other terminal connections. Excessive unshielded length, or
failure to connect cable shields properly, may also expose the unit to electrical noise,
resulting in an unstable meter reading.
Remote Transmitter Installation
34
Rosemount
®
8732EM Transmitter with HART Protocol Reference Manual
Summary of Contents for Rosemount 8732EM
Page 2: ......
Page 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Page 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 253: ...Implementing a Universal Transmitter Reference manual 247 ...