Product Certification
Rev 1.16
3.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at
.
3.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
3.3 North America
The US National Electrical Code
®
(NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined in
the respective codes.
3.4 USA
E5 FM Explosion-proof and Dust-Ignition proof
Certificate:
FM16US0090
Standards:
FM 3600:2011, FM 3615:2006, FM 3616:2011, FM 3810:2005,
ANSI/NEMA
®
-250:2003
Markings:
XP CL I, DIV 1, GP B, C, D T5; DIP CL II DIV 1 GP E, F, G; CL III; (–
20 °C ≤ T
a
≤ 80 °C); Seal not required; Type 4X
I5/IE FM Intrinsically Safe, Division 2/FISCO Intrinsically Safe
Certificate:
FM17US0348X
Standards:
FM 3600:2018, FM 3610:2018, FM 3611:2004, FM 3810:2005,
ANSI/NEMA 250:2003, ANSI/ISA-60079-0:2013, ANSI/
ISA-60079-11:2014, ANSI/ISA 61010-1:2004
Markings:
IS CL I, II, III, DIV 1, GP A, B, C, D, E, F, G T4; IS CL I, ZONE 0, AEx
ia IIC T4; (–20 °C ≤ T
a
≤ 60 °C); NI CL I, DIV 2, GP A, B, C, D T4; (–
20 °C ≤ T
a
≤ 60 °C); Install per 00752-1010; Type 4X FISCO Field
Device; IS CL I, II, III, DIV 1, GP A, B, C, D, E, F, G T4; IS CL I, ZONE