Foundation Fieldbus Block Information
53
Foundation Fieldbus Block Information
September 2018
Reference Manual
00809-0400-4728, Rev CA
LO_LIM
30
Out_Scale
Out_Scale
Not applicable
Read and Write
The setting for the alarm limit used to detect the LO
alarm condition.
LO_LO_ALM
36
Not applicable
None
Not applicable
Read only
The LO LO alarm data, which includes a value of the
alarm, a timestamp of occurrence and the state of the
alarm.
LO_LO_LIM
32
Out_Scale
Out_Scale
Not applicable
Read and Write
The setting for the alarm limit used to detect the LO LO
alarm condition.
LO_LO_PRI
31
0 – 15
None
1
Read and Write
The priority of the LO LO alarm.
LO_PRI
29
0 – 15
None
1
Read and Write
The priority of the LO alarm.
LOW_CUT
17
> = 0
Out_Scale
0
Read and Write
If percentage value of transducer input fails below this,
PV = 0.
MODE_BLK
05
Auto
Manual
Out of Service
None
Not applicable
Read and Write
The actual, target, permitted, and normal modes of the
block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
OUT
08
Out_Scale
± 10%
Out_Scale
Not applicable
Read and Write
The block output value and status.
OUT_D
37
Discrete_State 1 – 16
None
Disabled
Read and Write
Discrete output to indicate a selected alarm condition.
OUT_SCALE
11
Any output range
All available
none
Read and Write
The high and low scale values, engineering units code,
and number of digits to the right of the decimal point
associated with OUT.
PV
07
Not applicable
Out_Scale
Not applicable
Read only
The process variable used in block execution.
PV_FTIME
18
> = 0
Seconds
0
Read and Write
The time constant of the first-order PV filter. It is the
time required for a 63% change in the IN value.
SIMULATE
09
Not applicable
None
Disable
Read and Write
A group of data that contains the current transducer
value and status, the simulated transducer value and
status, and the enable/disable bit.
ST_REV
01
Not applicable
None
0
Read only
The revision level of the static data associated with the
function block. The revision value will be incremented
each time a static parameter value in the block is
changed.
STATUS_OPTS
14
Propagate fault forward
Uncertain if Limited
Bad if Limited
Uncertain if Man Mode
0
Read and Write
STDDEV
39
0 – 100
Percent
0
Read and Write
The average absolute error between the PV and its
previous mean value over that evaluation time defined
by VAR_SCAN.
STRATEGY
03
0 – 65535
None
0
Read and Write
The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the
block.
TAG_DESC
02
32 text characters
None
none
Read and Write
The user description of the intended application of the
block.
UPDATE_EVT
20
Not applicable
None
Not applicable
Read only
This alert is generated by any change to the static data.
XD_SCALE
10
Any sensor range
inH
2
O (68 °F)
inHg (0 °C)
ftH
2
O (68 °F)
mmH
2
O (68 °F)
mmHg (0 °C)
psi
bar
mbar
g/cm
2
kg/cm
2
Pa
kPa
torr
atm
deg C
deg F
AI1
= deg C
AI2 = deg C
In all Rosemount devices the units of the transducer
block is forced to match the unit code.
1.
The host system may write over default values pre-configured by Rosemount.
2.
Assume that when L_Type = Direct, the user configures Out_Scale which is equal to XD_Scale.
Table B-3. Definitions of AI Function Block System Parameters
Parameter
Index
no.
Available values
Units
Default
Read/Write
Description
Summary of Contents for Rosemount 644 FOUNDATION
Page 2: ......
Page 6: ...4 Reference Manual 00809 0100 4728 Rev CA Title Page September 2018 Title Page ...
Page 10: ...4 Reference Manual 00809 0400 4728 Rev CA Introduction September 2018 Introduction ...
Page 34: ...28 Reference Manual 00809 0400 4728 Rev CA Configuration September 2018 Configuration ...
Page 48: ...Reference Data September 2018 Reference Manual 00809 0400 4728 Rev CA Reference Data 42 ...
Page 63: ......