27
Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
1.9
Setting up 3DVison in DeltaV operate screen
Assumption
Modbus communications have been established between DeltaV and Rosemount 5708
3DMultiVision Server
Modbus register 49990 in the 5708 3DVision server software is being read via Modbus. Check if .enc
files do exist in the 3D image folder on the Application station (example: c:\3Dvision) and getting
updated
The 5708 3DVision server software has been installed and configured.
On the Application station share drive c: to everyone/read.
Microsoft .NET Framework 4.0 has been installed on the DeltaV operator station
Add button in DeltaV operate configure
1.
Launch
DeltaV Operate (Configure)
.
2.
Open desired operator graphic file.
3.
Select
Insert,
then
Push Button
.