2.
The scanner is connected to the Application station via RS485/USB or RS485/TCP converter. The
3DMultiVision software is installed on the Application station. The DeltaV VIM can read the scanner
data from the 3DMultiVision server on the Application station. Visualization of the 3D surface profile
on any DeltaV Operator station is possible.
After the configuration is complete, DeltaV and Rosemount 5708 3DMultiVision Server/Client will be
able to run in parallel when using a VIM card. The level variables will be able to be accessed by the
controller for indication and control by DeltaV. The application station will be able to use the
3DMultiVision software to setup the 3D Solids Scanner, show detail curves, and monitor values.
2.0
Specifications
The configuration presented here has been verified with the following specifications:
DeltaV supported version is 12.3 and above
Required support of Microsoft .NET Framework 4.0
VIMNet version 9.1.15.1
VIM version 3.10.16
3DMultiVision version 2.5.010 and above
The average update time of the parameters is approximately 15 seconds when using the VIM card setup.
The device can also be directly connected to a DeltaV serial card. The update time through the serial card
was approximately 10 seconds. Connection through the serial card prevents the 3DMultiVision software
from being used in parallel, and also requires manipulating the byte order manually to display the correct
values. When using the VIM card, the byte manipulation is handled automatically.