Table 7-6: Incorrect Level Readings
(continued)
Symptom
Possible causes
Recommended actions
When the product surface is near the
sloped tank bottom, the transmitter enters
alarm mode.
Level
Time
Reduction of projected
surface area close to sloping
tank bottom.
•
Verify the tank geometry parameters
are configured correctly (especially the
Reference Height and Bottom Offset).
•
If measurement in this region is not
crucial, increase the Empty Tank
Detection Area, see
.
•
Verify the Bottom echo visible when
tank is empty parameter is disabled,
see
Enable bottom echo visible when
(1)
= actual level
= reported level
7.3.2
Troubleshooting the 4-20 mA/HART
®
Output
Table 7-7: Troubleshooting the 4-20 mA/HART Output
Symptom
Recommended actions
Transmitter milliamp reading is zero.
•
Verify power is applied to signal terminals.
•
Verify power supply voltage is adequate at signal terminals,
see
•
Verify transmitter and power supply are properly grounded.
Transmitter milliamp reading is too low or high.
•
Verify level.
•
Check the settings of the 4-20 mA range values, see
.
•
Verify output is not in alarm condition.
•
Check that power wires are connected to the correct signal
terminals.
•
Perform Calibrate Analog Out, see
Milliamp reading is erratic.
•
Verify power supply voltage is adequate at signal terminals,
see
•
Check for external electrical interference.
•
Verify transmitter is properly grounded.
•
Verify shield for twisted pair is only grounded at the power
supply end.
•
Under turbulent conditions with low level rates, consider
increasing the Damping value.
Service and troubleshooting
Reference Manual
February 2020
00809-0100-4408
112
Reference Manual
Summary of Contents for Rosemount 5408
Page 4: ...4 ...
Page 8: ...Contents Reference Manual February 2020 00809 0100 4408 viii Reference Manual ...
Page 10: ...Introduction Reference Manual February 2020 00809 0100 4408 10 Reference Manual ...
Page 20: ...Transmitter overview Reference Manual February 2020 00809 0100 4408 20 Reference Manual ...
Page 72: ...Mechanical installation Reference Manual February 2020 00809 0100 4408 72 Reference Manual ...
Page 100: ...Operation Reference Manual February 2020 00809 0100 4408 100 Reference Manual ...
Page 240: ...Product certifications Reference Manual February 2020 00809 0100 4408 240 Reference Manual ...
Page 242: ...Product certifications Reference Manual February 2020 00809 0100 4408 242 Reference Manual ...
Page 244: ...Product certifications Reference Manual February 2020 00809 0100 4408 244 Reference Manual ...
Page 246: ...Product certifications Reference Manual February 2020 00809 0100 4408 246 Reference Manual ...
Page 248: ...Product certifications Reference Manual February 2020 00809 0100 4408 248 Reference Manual ...