Quick Installation Guide
00825-0500-4809, Rev CA
September 2003
Threaded Flo-Tap 485 Annubar
S
TEP
8
CONTINUED
...
Recommended Installations
Gas Service
Secure the electronics above the sensor to prevent condensable
liquids from collecting in the impulse piping and the DP cell.
Liquid Service (up to 250 °F (121 °C))
Secure the electronics below the sensor to ensure that air will not be
introduced into the impulse piping or the electronics.
Figure 12. Gas
Figure 13. Liquid