![Emerson Rosemount 3152 Reference Manual Download Page 75](http://html.mh-extra.com/html/emerson/rosemount-3152/rosemount-3152_reference-manual_104708075.webp)
Reference Manual
00809-0100-4835 Rev BE
February 2018
Rosemount 3150 Series
Maintenance & Troubleshooting
66
Table 5-3 – Troubleshooting
SYMPTOM
POTENTIAL
SOURCE
CORRECTIVE ACTION
High Output
Primary Element
Check for restrictions at primary element, improper installation or
poor condition. Note any changes in process fluid properties that
may affect output.
Impulse Piping
•
Check for leaks or blockage.
•
Ensure blocking valves are fully open.
•
Check for entrapped gas in liquid lines, or liquid in dry lines.
•
Ensure that density of fluid in impulse line is unchanged.
•
Check for sediment in transmitter process flanges.
Transmitter
Electronics
Make sure that filter pins and the sensor module connections are
clean. If the electronics are still suspect, substitute new
electronics.
Transmitter
Electronics Failure
Determine faulty circuit board by trying spare electronics
assembly or terminal block assembly. Replace faulty assembly.
Sensor Module
NOTE: S
ee
section. The sensing
element is not field repairable and must be replaced if found to be
defective. See
disassembly. Check for obvious defects (i.e. punctured isolating
diaphragm, etc.) and contact Rosemount Nuclear.
Power Supply
Check the power supply output voltage at the transmitter.
Low Output
or No Output
Primary Element
Check the installation and condition of primary element.
Note any changes in process fluid properties that may affect
output.
Loop Wiring
CAUTION
Do not use more than 55 volts to check the loop, or
damage to the transmitter electronics may result.
•
Check for inadequate voltage to the transmitter.
•
Check the milliamp rating of the power supply against the total
current being drawn for all transmitters being powered.
•
Check for intermittent shorts, open circuits, or multiple grounds.
•
Check for proper polarity at the signal terminal.
•
Check loop impedance.
•
Check wire insulation to detect possible shorts to ground.
Impulse Piping
•
Ensure that the pressure connection is correct.
•
Check for leaks or blockage.
•
Check for entrapped gas in liquid lines, or liquid in dry lines.
•
Check for sediment in transmitter process flanges.
•
Ensure that blocking valves are fully open and that bypass
valves are tightly closed.
•
Ensure that density of fluid in the impulse line is unchanged.
Transmitter
Electronics
Connections
•
Ensure that calibration adjustments are in allowable range.
•
Check for short in sensor leads.
•
Make sure filter pins are clean, and check the sensor module
connections.
•
If the electronics are still suspect, substitute new electronics.
Continued on Next Page