Electrical Installations
May 2017
Electrical Installations
Transmitter case grounding
Always ground the transmitter case in accordance with national and local electrical codes. The most
effective transmitter case grounding method is a direct connection to earth ground with minimal
impedance. Methods for grounding the transmitter case include:
Internal ground connection: the internal ground connection screw is inside the FIELD TERMINALS side
of the electronics housing. This screw is identified by a ground symbol (
). The ground connection
screw is standard on all Rosemount 3051P Transmitters. Refer to
External ground connection: The external ground connection is located on the exterior of the
transmitter housing. Refer to
. This connection is only available with option T1.
Figure 4-8. Internal Ground Connection
A. Internal ground location
B. External ground location
C. Positive
D. Negative
E. Test
Note
Grounding the transmitter case via threaded conduit connection may not provide sufficient ground
continuity.
Transient protection terminal block grounding
The transmitter can withstand electrical transients of the energy level usually encountered in static
discharges or induced switching transients. However, high-energy transients, such as those induced in
wiring from nearby lightning strikes, can damage the transmitter.
The transient protection terminal block can be ordered as an installed option (Option Code T1) or as a
spare part to retrofit existing Rosemount 3051P Transmitters in the field. See
for part numbers. The lightning bolt symbol shown in
identifies the
transient protection terminal block.
C
D
E
A
B
Summary of Contents for Rosemount 3051P
Page 2: ......
Page 8: ...6 Reference Manual 00809 0700 4001 Rev AA Contents May 2017 Contents ...
Page 12: ...2 Reference Manual 00809 0700 4001 Rev AA Introduction May 2017 Introduction ...
Page 36: ...26 Reference Manual 00809 0700 4001 Rev AA Configuration May 2017 Configuration ...
Page 74: ...64 Reference Manual 00809 0700 4001 Rev AA Troubleshooting May 2017 Troubleshooting ...
Page 109: ......