Note
The write lock switch can be left in the locked or unlocked
position. The simulate enable/disable switch may be in either
position for normal device operation.
2.5.4
Manual setup of the AI block configuration
This procedure describes the manual setup of the AI Block Configuration.
Prerequisites
Navigate to
Configure
→
Manual Setup
→
Process Variable
.
Note
When using manual setup perform the steps in the order described in
Figure 2-7: Configuration Flowchart
Start
Device Configuration
here
1. Verify device tag:
PD_TAG
7. Set damping:
PRIMARY_VALUE_
DAMPING
8. Set up LCD display
6. Set low cutoff:
LOW_CUT
9. Review transmitter
configuration
3. Set signal
conditioning:
L_TYPE
5. Set scaling
OUT_SCALE
2. Check switches and
software write lock
Done
10. Set switches and
software write lock
4. Set scaling
XD_SCALE
Note
For convenience, AI block 1 is pre-linked to the transmitter primary variable
and should be used for this purpose. AI block 2 is pre-linked to the
transmitter sensor temperature. The channel must be selected for AI blocks
3 and 4.
•
Channel 1 is the primary variable.
•
Channel 2 is the sensor temperature.
If the F
OUNDATION
™
Fieldbus Diagnostics Suite Option Code D01 is enabled,
these additional channels are available.
•
Channel 12 is the SPM mean.
•
Channel 13 is the SPM standard deviation.