Figure 3-2: Connections Overview for Type 'DE' Housings
A
B
A. Connection terminals (in a terminal box for increased safety).
The fixing torque is 0.5 - 0.6 Nm
B. Protective conductor terminal - Protective Earth (PE)
3.3.1
Wiring the SPDT relay
Power supply:
•
19 to 230 Vac (50/60 Hz) +10% 8 VA
•
19 to 55 Vdc +10% 1.5 W
Signal output (floating SPDT relay):
•
Maximum 250 Vac, 8 A, non-inductive
•
Maximum 30 Vdc, 5 A, non-inductive
Fuse on signal output: maximum 10 A, slow or fast, HBC, 250 V
Figure 3-3: SPDT Power Supply and Signal Output Connections
3 4
1 2
5
PE
Signal output
Power supply
+
-
L N
October 2020
Quick Start Guide
Quick Start Guide
19