5. Select the
Configure>Manual Setup
option.
6. Set the device to Out Of Service (OOS) mode by clicking the
Change
button.
7. Select the desired tab (Device, Multiple Analog Output Block Mapping, Tank Name etc.) and configure
the device.
8. The Device tab lets you configure display units, display view and language. It also provides the option
to write protect the Rosemount 2230 (see
“Write protection” on page 107
9. In addition to the Device tab there are various tabs that give you access to options such as block
parameter mapping, configuration of custom parameters and units, as well as tank name
specification as shown below.
10.When configuration is finished, click the
Send
button to store the current configuration in the device
database.
11.Press the
Change
button to set the device back to operating (Auto) mode.
12.Press the
Close
button to close the window.
Manual Setup
Configure
Change Mode