Reference Manual
00809-0100-4029, Rev AA
July 2005
Rosemount 2110
2-4
Electrical Installation
Mode Selection
Mode Selection by customer wiring.
Code
0
1
Load Switching: ac/dc
Direct load switching: ac/dc
PNP Output: dc
NP for PLC/SPS connection: dc
DRY = ON: High level alarm
PE (Ground)
PE (Ground)
WET = ON: Low level alarm
PE (Ground)
PE (Ground)
Maximum inrush current: 5A (Over current protected)
I Maximum continuous: 500 mA
I Minimum continuous: 20mA
Supply current: 3mA nominal
Voltage drop: 6.5V @ 24V dc /
5.0V @ 240 V ac
Voltage drop: <3V
I Load off: <3mA
I Load off: <0.5mA
1
3
R
2A(T)
21-264V ac 50/60Hz
21-264V dc
L1
+V
N
0V
1
3
R
2A
(T)
2
0V
+V (18-60V dc)
PLC
Input
1
R
2A
(T)
21-264V ac 50/60Hz
21-264V dc
L1
+V
N
0V
2
1
3
R
2A
(T)
2
0V
+V
(18-60V dc)
PLC
Input
R = External Load
(must be wired)
= External Load