78
Reference Manual
00809-0100-4107, Rev BA
Section 5: Operation and Maintenance
April 2013
5.7
Switching HART Revision
Some systems are not capable of communicating with HART Revision 7 devices. The following
procedures list how to change HART revisions between HART Revision 7 and HART Revision 5.
5.7.1
Switching HART revision with Generic Menu
If the HART configuration tool is not capable of communicating with a HART Revision 7 device, it
should load a Generic Menu with limited capability. The following procedures allow for
switching between HART Revision 7 and HART Revision 5 from a Generic Menu.
1.
Locate "Message" field
a.
To change to HART Revision 5, Enter:
HART5
in the message field
b. To change to HART Revision 7, Enter:
HART7
in the message field
5.7.2
Switching HART Revision with Field Communicator
From the HOME screen, enter the fast key sequence and follow steps within the Field
Communicator to complete the HART revision change.
5.7.3
Switching HART Revision with AMS Device Manager
1.
Click on
Manual Setup
and select
HART
2.
Select
Change HART Revision
then follow the on screen prompts.
Note
AMS Device Manager versions 10.5 or greater are compatible with HART Revision 7.
5.7.4
Switching HART revision with Local Operator Interface
Navigate to
HART REV
within the extended menu and select if either
HART REV 5
or
HART REV 7
.
below to change HART Revision.
From the
HOME
screen, enter the fast key sequence
HART5
HART7
Device Dashboard Fast Keys
2, 2, 5, 2, 4
2, 2, 5, 2, 3