19
Reference Manual
00809-0100-4100, Rev AA
Section 2: Configuration
June 2012
2.8.2
Set Transfer Function
The 3051 Wireless has two output settings: Linear and Square Root. Activate the square root
output option to make output proportional to flow. As input approaches zero, the 3051
Wireless automatically switches to linear output in order to ensure a more smooth, stable
output near zero (see
).
From 0 to 0.6 percent of the ranged pressure input, the slope of the curve is unity (y = x). This
allows accurate calibration near zero. Greater slopes would cause large changes in output (for
small changes at input). From 0.6 percent to 0.8 percent, curve slope equals 42 (y = 42x) to
achieve continuous transition from linear to square root at the transition point.
To select the output transfer function:
1.
From the
Home
screen, select 2: Configure.
2.
Select 2: Manual Setup.
3.
Select 2: Pressure.
4.
Select 2: Transfer Function and choose either Linear or Square Root.
Figure 2-2. Square Root Output Transition Point
Fast Keys
2, 2, 2, 2
Sq. Root
Curve
Transition Point
Linear Section
Slope=1
Slope=42
Transition Point
Sq. Root Curve
Full Scale
Flow (%)
Summary of Contents for Rosemount 2051 Wireless Series
Page 2: ......
Page 12: ...4 Reference Manual 00809 0100 4102 Rev AA Section 1 Introduction June 2012 Introduction ...
Page 32: ...24 Reference Manual 00809 0100 4102 Rev AA Section 2 Configuration June 2012 Configuration ...
Page 110: ......
Page 113: ......
Page 117: ...iv Reference Manual 00809 0100 4100 Rev AA Title Page June 2012 ...
Page 123: ...x Reference Manual 00809 0100 4100 Rev AA Table of Contents June 2012 Table of Contents ...
Page 167: ...44 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Page 168: ...45 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Page 169: ...46 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Page 249: ......