4.2.4
Closed tank example (non-zero based lower range value)
Note
For F
OUNDATION
™
Fieldbus, refer to the AI Function Blocks in reference manual.
Figure 4-12: Tuned-System
Procedure
1. Set seals at the same elevation for bench pressure verification, if required to range
transmitter. If the transmitter does not require bench pressure verification, proceed
to
Bench pressure verification
Power and range the transmitter using a Field Communicator to the required tank
span. (
example) With the required calibration fixture attached to the
seal assemble apply pressure.
4 mA = 0 inH
2
O
20 mA = 81 inH
2
O
2. Install the tuned system by assembling the seals to the process taps. Common
practice is to mount the high-pressure side seal to the low process tap and the low-
pressure side seal to the high process tap.
3. Wire and apply power to the transmitter.
4. If the transmitter has a zero button, see
, push the Zero
button. This will automatically re-range the transmitter so the LRV (4 mA) will equal
the current applied pressure value and the URV (20 mA) will be adjusted to the
required calculated span.
Example 1: Re-range using transmitter zero button
:
Reference Manual
Configuration
00809-0100-4002
May 2020
Rosemount DP Level
85
Summary of Contents for Rosemount 1199
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual May 2020 00809 0100 4002 8 Rosemount DP Level ...
Page 22: ...Remote Seal Systems Reference Manual May 2020 00809 0100 4002 22 Rosemount DP Level ...
Page 74: ...Installation Reference Manual May 2020 00809 0100 4002 74 Rosemount DP Level ...
Page 92: ...Fill Fluids Reference Manual May 2020 00809 0100 4002 92 Rosemount DP Level ...