12.3 Optional external EMC filters
EMC filters can be sourced directly from Schaffner and Epcos. See
Table 12-33 for details.
Table 12-33 Quantum MP and EMC filter cross reference
* This filter is required if the input current to the Quantum MP will be
greater than 66Amps.
12.3.1 Typical short-term overload limits
The maximum percentage overload limit changes depending on the
selected motor
Variations in motor rated current will result in changes in the maximum
possible overload as detailed in the
Advanced User Guide
.
Figure 12-1 can be used to determine the maximum overload duration
available for overloads between 100% and 150%. For example the
maximum overload available for a period of 60 seconds is 124%.
Figure 12-1 Maximum overload duration available
Overload of 150% for 30s is available with ambient temperature of 40
C up to a maximum of 10 repetitions per hour.
It is essential that line rectors be connected between the filter
terminals and the power input terminals. Failure to observe
this requirement could result in destruction of the thyristors.
CAUTION
Model
Manufacturers part number
Schaffner armature
standard
Schaffner armature
high performance
Epcos
armature
high performance
Schaffner standard
field filter
Epcos standard
field filter
QMP45A4(R)
FN3270H-80-35
FN3258-75-52
B84143-A66-R105
FN3280H-8-29
W62400-T1262
QMP75A4(R)
*B84143-A90-R105
QMP155A4(R)
FN3270H-200-99
FN3258H-180-40
B84143BO250S080
QMP210A4(R)
QMP350A4(R)
N/A
FN3359-800-99
N/A
FN3280H-8-29
N/A
QMP400A4(R)
QMP550A4(R)
QMP700A4(R)
100
105
110
115
120
125
130
135
140
145
150
155
160
0
10
20
30
40
50
60
70
80
90
100
11
0
120
130
140
150
160
170
180
200
overload duration (seconds)
overload
(%)
NOTE