The Service Request Function
177
Function #
Description
9
Read Sweep Time from Beginning of Sweep
10
Read Folder Name
11
Read PLC ID
12
reserved
13
Shut Down the PLC
14
Clear Fault Tables
15
Read Last-Logged Fault Table Entry
16
Read Elapsed Time Clock
17
reserved
18
Read I/O Override Status
19-22
reserved
23
Read Master Checksum
26/30
Interrogate I/O
27, 28
reserved
29
Read Elapsed Power Down Time
31-255
reserved
11.2
Format of the SVCREQ Function
The SVCREQ function has three inputs and one output.
Figure 171
When the SVCREQ receives power flow, the PLC is requested to perform the function
number FNC indicated. Parameters for the function are located beginning at the reference
given for PARM. This is the beginning of the “parameter block" for the function. The number
of 16-bit references required depends on the SVCREQ function being used.
Parameter blocks may be used as both inputs for the function and the location where data
may be output after the function executes. Therefore, data returned by the function is
accessed at the same location specified for PARM.
The SVCREQ function passes power flow unless an incorrect function number, incorrect
parameters, or out-of-range references are specified. Specific SVCREQ functions have
additional causes for failure.