Status Address, Length: The Status Address is the reference memory location for the 32 bits
of status data associated with the PROFINET Controller itself. The Status address can be
assigned to valid %I, %Q, %R, %AI, %AQ, %W, %G, %T or %M memory by right-clicking on the
Status Address field and selecting the Data Entry tool. The default value is the next available
%I address. See Section 5:, Diagnostics, for definitions of the status bits that the module
writes to this address.
Figure 42: Setting the Status Reference Address
Note:
Because point faults are not supported by %G, %T and %M, the other available memory
types, or I/O Symbolic, are preferred.
SFP Cage 1 / 2 / 3 / 4: If the PNC001module will use plug
–
in Small Form-factor Pluggable
devices in Port 3 and/or Port 4, specify the SFP devices in the appropriate field(s). On the
Settings tab, right-click in the Values field for the port, and select Data Entry tool to open
the Catalog window. In the Catalog window, select the type of SFP device for the port, as
shown in Figure 43, and click OK. If the device is not listed, choose GENERIC_SFP to add it
to the configuration.
Figure 43: Select SFP Device from Catalog
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...