RSTI-EP PROFINET I/O Controller User Manual
Section 2
GFK-2571R
May 2021
Installation
41
2.8
PNC001 LED Behavior
2.8.1
Power-up LED Patterns
At power-up, the LEDs show the blink patterns described below. The LEDs also blink
diagnostic patterns for certain operating errors and for module identification. See Section
5:, Diagnostics for a description of those special blink patterns.
Step LED/Blink
pattern
Description
Figure 31: PNC001-Bxxx Front
View showing LEDs
1
All LEDs OFF
Normal operation
1.1
ACTIVE LED
solid green
(PNC001-Bxxx
only)
Normal operation
1.2
CONFIG LED
solid green
(PNC001-Bxxx
only)
Normal operation
2
STATUS LED
solid green
Normal operation
OK LED blinks
Amber with
special blink
code
Fatal Initialization or
Diagnostics Failure, Hardware
Module Identity Information
not available
OK, LAN, and
STATUS LEDs
blink green in
unison (1 Hz)
Invalid firmware detected.
Module is waiting for firmware
update. Blink pattern continues
during firmware update.
3
LAN and
STATUS LED
solid green
(PNC001-Ax
only)
Normal operation
4
LAN LED solid
green
Normal operation
LAN and
STATUS LED
blink green
(1 Hz)
Update of module firmware.
After the automatic update
completes, the LEDs blink
Amber and the module resets,
which restarts the power-up
process.
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...