Module Installation 

The ECM850 must be installed in the main (CPU) rack of an RX3i 
system,  using  a  Universal  Backplane  such  as

 

IC695CHS007,

 

CHS012  or  CHS016.  The  ECM850  supports  insertion/removal 
while power is applied to the system (hot swap). This module is 
compatible 

with 

RX3i 

CPU 

models 

CPU320,CPU315,CPE305,CPE310 and CRU320. 

Summary of Contents for PACSystems RX3i IC695ECM850

Page 1: ...QUICK START GUIDE GFK 2851A Sep 2019 PACSystemsTM RX3i IEC 61850ETHERNETCOMMUNICATIONMODULE IC695ECM850 ...

Page 2: ...l Checks 13 2 2 Installation Location 14 2 3 Installation in Hazardous Areas 14 2 4 Module Installation 16 2 5 Ethernet Port Connections to IEC 61850 LAN 19 3 Configuration 23 3 1 Confirm ECM850 Communication with the CPU 23 3 2 Next Steps 24 4 Status and Diagnostic Data 27 4 1 Module Status Data 32 bits 27 4 2 Problems during Powerup and Reset 28 5 Additional Information 30 5 1 PACSystems RX3i Us...

Page 3: ...nattention could cause either personal injury or damage to equipment a Warning notice is used arning Caution Caution notices are used where equipment might be damaged if care is not taken arning Note Notes merely call attention to information that is especially significant to understanding and operating the equipment These instructions do not purport to cover all details or variations in equipment...

Page 4: ...nced herein or to the document itself at any time This document is intended for trained personnel familiar with the Emerson products referenced herein Emerson may have patents or pending patent applications covering subject matter in this document The furnishing of this document does not provide any license whatsoever to any of these patents Emerson provides the following document and the informat...

Page 5: ...telligent Electronic Devices IEDs IEC 61850 Servers on the network using the IEC 61850 protocol 1 2 3 4 ECM850 ACTIVE USB OK LAN STATUS CONN USB IP ADDRESS MAC ADDRESS PORTS TO INSTALL TORQUE TO 6 IN LB FRONT 3 4 1 2 SD CARD USB port Micro Type B IEC 61850 Port Activity Indicator LEDs 1 4 USB Port Activity Indicator LEDs ACTIVE USB Module Status Indicator LEDs OK LAN STATUS CONN SD Card Slot Reset...

Page 6: ... its four external Ethernet ports Two 8 conductor RJ 45 shielded twisted pair 10 100 1000 Mbps copper interfaces and two Small Form factor Pluggable SFP cages provide flexibility in media selection Figure 1 2 Ethernet Ports The module is assigned five Ethernet MAC addresses one for each of the four external Ethernet ports and one for the internal switch ...

Page 7: ...low SFP devices can be removed and replaced during module operation SFP Type Wave length nm Medi a Type Core Size μm Modal Bandwidth MHz Km Distance m 100BASE FX1 1300 MMF 62 5 500 2 2 000 Full Duplex 2 400 Half Duplex 50 400 50 500 100BASE LX10 1300 SMF 9 2 10 000 1000BAS E SX 850 MMF 62 5 160 2 220 200 2 275 50 400 2 500 500 2 550 1000BAS E LX 1300 SMF 9 2 10 000 ...

Page 8: ...6 100 max 1 Emerson part number IC695SPF002 2 Emerson part number IC695SPC100 1 3 Micro USB Port The ECM850 has a USB Micro B socket for connection to a computer It can be used to access the ECM850 s Command Line Interface function following the installation of special drivers This port is intended for advanced maintenance and is not required for normal use See the User Manual referenced in Sectio...

Page 9: ...Indicators LEDs OK indicates whether the module is able to perform normal operations Green ON steady OK Green blink pattern Fatal error Flashes once between error codes blinked on the STATUS LED OFF Not OK LAN indicates access to and activity on the Ethernet local area network LAN The LAN LED indicates network packets are being processed by the network interface not just passing through the embedd...

Page 10: ...uring normal operation It is reset when the local log is cleared For more information see the Command Line Interface clear log command Green ON No new local log table entries OFF New local log table entry Green blink pattern Fatal error Error codes are blinked on this LED See Chapter 5 of the User Manual for details Red blinking Invalid MAC address all MAC addresses are validated error indicates i...

Page 11: ...r Flashes once between error codes blinked on the STATUS LED ACTIVE indicates the status of IEC 61850 connections Green ON All configured IEC 61850 IEDs have established IEC 61850 connections Amber ON At least one configured IEC 61850 IED has established a connection but at least one configured IED is not connected OFF No configured IEDs have established connections to the ECM850 or hardware confi...

Page 12: ...Quick Start Guide Chapter 1 GFK 2851A Sep 2019 User Features 11 USB indicates activity on the USB port Green Blinking USB port activity OFF No USB port activity ...

Page 13: ...t ports Blue ON Link connected 1000 Mbps Blue blinking Port active 1000 Mbps Green ON Link connected 100 Mbps Green blinking Port active 100 Mbps Purple ON Link connected 10 Mbps Purple blinking Port active 10 Mbps Green blink pattern Fatal error Flashes once between error codes blinked on the STATUS LED OFF The associated Ethernet port is not connected to an active link Red ON Port 3 and port 4 o...

Page 14: ... claim with the carrier for damage incurred during shipment Emerson Electric Company will fully cooperate with you however should such action be necessary After unpacking the RX3i equipment record all serial numbers Serial numbers are required if you should need to contact Customer Care during the warranty period All shipping containers and all packing material should be saved should it be necessa...

Page 15: ...This equates to a NEMA UL Type 1 enclosure or an IP20 rating IEC60529 providing at least a pollution degree 2 environment For details about installing RX3i rack systems refer to GFK 2314 If you need technical help contact Technical Support weblink https www emerson com Industrial Automation Controls support 2 3 Installation in Hazardous Areas The following information is for products bearing the U...

Page 16: ...BEFORE REPLACING OR WIRING MODULES AND DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS EXPLOSION HAZARD USB PORT IS ONLY FOR USE IN NONHAZARDOUS LOCATIONS DO NOT USE UNLESS AREA IS KNOWN TO BE NON HAZARDOUS ATEX Zone 2 The ECM850 must be mounted in an enclosure certified in accordance with EN60079 15 for use in Zone 2 Group IIC and ...

Page 17: ...e ECM850 must be installed in the main CPU rack of an RX3i system using a Universal Backplane such as IC695CHS007 CHS012 or CHS016 The ECM850 supports insertion removal while power is applied to the system hot swap This module is compatible with RX3i CPU models CPU320 CPU315 CPE305 CPE310 and CRU320 ...

Page 18: ...e into the backplane remove the plastic knockout in the slot where the module will be placed see figure Figure 2 1 Backplane The installation slot must match the slot that is selected in the module s hardware configuration in the PAC Machine Edition application Module Insertion RX3i rack power may be off or on hot insertion Holding the module firmly align the module with the correct slot and conne...

Page 19: ... heat sink screw on the front of the module several turns into the threaded hole in the backplate using a flat tip screwdriver but do not tighten Insert the two provided M3x5 machine screws through the module s bottom bracket into threaded holes in the bottom of the backplate and screw them several turns using a 1 Phillips screwdriver but do not tighten Tighten the heat sink screw to 6 in lbs 0 7 ...

Page 20: ... port automatically detects the attached cable and functions properly with either straight through or crossover cables Note The ECM850 operates only in autonegotiate mode All IEC 61850 devices and switches that are connected to the ECM850 should be configured to use autonegotiation IEC 61850 LAN Topologies There are three basic topologies that can be used alone or in combination for connecting an ...

Page 21: ...2 GFK 2851A Sep 2019 Hardware Installation 20 Direct The simplest scheme is the direct connection of IEDs to the ports of the ECM850 This limits the number of IEDs served by an ECM850 to four Figure 2 2 Direct Connection of IEDs ...

Page 22: ...1A Sep 2019 Hardware Installation 21 Linear Some IEDs are provided with at least two Ethernet ports and an internal Ethernet switch allowing them to be connected in a daisy chain as shown below Figure 2 3 IEDs connected in a daisy chain ...

Page 23: ...means of one or more network switches The diagram below shows a single ECM850 port connected to one port of a switch leaving the remainder of the switch s ports available for connection to IEDs If more IEDs must be connected more switches can be connected to the ECM850 s other ports or additional switches can be connected to the first Figure 2 4 IEDs connected with network switches ...

Page 24: ...y Description ICD or Configured IED Description CID files for the devices in your system available from the device manufacturers PACSystems RX3i IEC 61850 Ethernet Communication Module User Manual GFK 2849 available from the Emerson support website https www emerson com en us support You will need to refer to this manual to fully configure and commission the ECM850 3 1 Confirm ECM850 Communication...

Page 25: ...850 is displayed in the list similar to the following screenshot it indicates that the module has powered up as expected is communicating with the CPU over the rack backplane and that it is ready for further configuration 3 2 Next Steps The full configuration of the ECM850 is beyond the scope of this Guide but is covered in detail in the User Manual GFK 2849 referenced in section 5 In brief the st...

Page 26: ...with which the ECM850 will communicate The IEC 61850 Configurator supports both online and offline configuration Online the user can connect to the IED and browse the device s data model to select objects of interest Offline the user can import an IED Capability Description ICD or Configured IED Description CID file preconfigured by the IED vendor to browse and select the device s data objects Mac...

Page 27: ...Quick Start Guide Chapter 3 GFK 2851A Sep 2019 Status and Diagnastic Data 26 downloaded to the RX3i controller for validation and deployment ...

Page 28: ...onnected to another device and is operating correctly 0 indicates the port is not connected to another device the port has an error preventing communications or the SFP cage is empty or has an incompatible SFP device 3 Port2 Link Up 4 Port3 Link Up 5 Port4 Link Up 6 8 Reserved Always 0 9 All Devices Connected 1 indicates all configured devices are connected and communicating over IEC61850 protocol...

Page 29: ...re 11 32 Reserved Always 0 4 2 Problems during Powerup and Reset Certain conditions can prevent the module from becoming operational Problem Indication Action Hardware failure All Indicator LEDs off Module unresponsive Return the module to Emerson Invalid bootstrap image Invalid boot image No Indicator LEDs turn on and the module is unresponsive or The STATUS LED is solid green and is the only LED...

Page 30: ...stomer Service Non fatal initialization failure Module powers up normally but an entry is added to the Local Log table and the RX3i CPU fault table Note the fault and contact Customer Service Module does not contain hardware identity info Fatal Error LED blink code Note the blink code and contact Customer Service ...

Page 31: ... IEC 61850 Ethernet Communication Module Important Product Information GFK 2850 User manuals product updates and other information sources are available on the Support website https www emerson com Industrial Automation Controls support under Controllers and IO RX3i Controllers 5 2 Information about IEC 61850 For detailed information about the IEC 61850 standard contact the International Electrote...

Page 32: ...right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson product remains solely with the purchaser 2019 Emerson All rights reserved Emerson Terms and Conditions of Sale a...

Reviews: