Detailed Description of I/O Modules
352
5.32.3
Modifiable Parameters for EP-3704
Channel
Description
Options
Default
Temperature unit
Degree Celsius (0) /
Degree Fahrenheit (1) /
Kelvin (2)
Degree Celsius
0 - 3
Measurement range
PT100 -200 ... 850 Degree Celsius (0) /
PT200 -200 ... 850 Degree Celsius (1) /
PT500 -200 ... 850 Degree Celsius (2) /
PT1000 -200 ... 850 Degree Celsius (3) /
NI100 -60 ... 250 Degree Celsius (4) /
NI120 -80 ... 260 Degree Celsius (5) /
NI200 -60 ... 250 Degree Celsius (6) /
NI500 -60 ... 250 Degree Celsius (7) /
NI1000 -60 ... 250 Degree (8) /
Cu10 -100 ... 260 Degree Celsius (9) /
Resistance 40 Ω (10) /
Resistance 80 Ω (11) /
Resistance 150 Ω (12) /
Resistance 300 Ω (
13) /
Resistance 500 Ω (14) /
Resistance 1 kΩ (15) /
Resistance 2 kΩ (16) /
Resistance 4 kΩ (17) /
disabled (18)
disabled
0 - 3
Connection type
2-wire (0) /
3-wire (1) /
4-wire (2)
2-wire
0 - 3
Conversion time
240ms (0) /
130ms (1) /
80ms (2) /
55ms (3) /
43ms (4) /
36ms (5)
80ms
0 - 3
Channel diagnostics
disabled (0) / enabled (1)
disabled
0 - 3
Limit value monitoring
disabled (0) / enabled (1)
disabled
0 - 3
High limit value
-32,768 ... 32,767
0
0 - 3
Low limit value
-32,768 ... 32,767
0