IC695CPE400 Rackless CPU Quick Start Guide
GFK-3002G
Installation in Hazardous Areas
Refer to the Installation and Maintenance Requirements document, GFK-
3004.
Connect to Power Supply
The 24Vdc power input connector is located
on the underside of the CPE400, as shown in
Figure 8. The signal pinouts are also
indicated.
The mating connector for the CPE400 24Vdc
power input is the 3-pin Phoenix 1827716
shown in Figure 9. The power supply cable
prepared by the user must use the specified
mating connector.
The positive
“+”
and negative
“
-
”
signals are
required. FGND is optional but
recommended.
For the mating connector, the compatible
conductor size is from 24AWG to 16AWG.
Strip the wires back 7mm before inserting
into the connector. Tightening torque for
the three signal screws is 2.2 in-Ibs
(0.248Nm). Secure the mating connector to
the power input connector via the two
captive screws provided.
Figure 8: 24 VDC Power
Input Connector