13
IC695CPE400 Rackless CPU Quick Start Guide
GFK-3002G
Reference Manual,
GFK-2222 or later. For more detailed information
regarding Field Agent, refer to the
Field Agent User’s Guide,
GFK-2993.
The FAOK LED, located on the front panel, indicates the status of the Field
Agent interface.
Energy Pack Connector
The CPE400 compatible Energy Pack, IC695ACC403, is supplied with a
purpose-built cable, IC695CBL003, which installs in the 24 VDC In and
Energy Pack Control & Status connectors shown in Figure 2. Use of the
Energy Pack is optional. When used, it allows the CPE400 to save its current
state upon loss of power. Refer to the
PACSystems RX3i Rackless Energy Pack
IC695ACC403 Quick Start Guide,
GFK-3000, for complete wiring and
grounding instructions.
Input Power Connector
If no Energy Pack is to be connected, refer to the section entitled
. Otherwise, refer to the
PACSystems RX3i Rackless Energy Pack
IC695ACC403 Quick Start Guide,
GFK-3000.
Removable Data Storage Device (RDSD)
The CPE400 is equipped with a micro-SD card slot and two USB ports. These
are not currently supported.