Device Setup
E2 Serial Port Setup
1. Log into the E2 controller.
2. Press
I
,
,
, and
(General Controller Information), then press
B
twice to move to
the
C3: Serial
tab.
3. Press the down arrow key to the
COM Connection
where the device is wired.
4. Press
D
(LOOK UP)
and select
MODBUS-1
,
MODBUS-2
or
MODBUS-3
, then press
>
to set
configuration.
5. Press
D
to select options and set the MODBUS connection as follows:
6. Press
>
to set configuration, then
J
to save changes.
7. Press
H
to return to the
Home screen
.
MODBUS Connection
COM Baud:
19200 Baud
COM Data Size:
8
COM Parity
Even
COM Stop Bits:
1
Figure 1 - E2 Device and COMM Setup