Device Setup

E2 Serial Port Setup

1. Log into the E2 controller.

2. Press 

I

, and 

 (General Controller Information), then press 

B

 twice to move to 

the 

C3: Serial

 tab.

3. Press the down arrow key to the 

COM Connection

 where the device is wired.

4. Press 

D

 (LOOK UP)

 and select 

MODBUS-1

MODBUS-2

 or 

MODBUS-3

, then press 

>

 to set 

configuration.

5. Press 

D

 to select options and set the MODBUS connection as follows:

6. Press 

>

to set configuration, then 

J

 to save changes.

7. Press 

H

 to return to the 

Home screen

.

MODBUS Connection 

COM Baud:

19200 Baud

COM Data Size:

8

COM Parity

Even

COM Stop Bits:

1

Figure 1 - E2 Device and COMM Setup

Summary of Contents for MRLDS-450

Page 1: ...0 425 2724 Option 4 Note UltraSite32 software should be installed to perform a description file upload Connect to E2 using UltraSite32 1 Launch UltraSite program and login 2 View the Directory Level and then Site Level 3 Right click Site Level and click Connect 4 Locate the E2 where the MRLDS_450 dsc will be installed 5 Right click the unit and select Upload Description File 6 Click Browse to sele...

Page 2: ...roller Information then press Btwice to move to the C3 Serial tab 3 Press the down arrow key to the COM Connection where the device is wired 4 Press D LOOK UP and select MODBUS 1 MODBUS 2 or MODBUS 3 then press to set configuration 5 Press Dto select options and set the MODBUS connection as follows 6 Press to set configuration then Jto save changes 7 Press Hto return to the Home screen MODBUS Conn...

Page 3: ...ess Ithen and to enter Connected I O Boards and Controllers 2 Press Bto move to the C3 ECT tab Highlight the MRLDS 450 application and enter the desired number of devices under Quantity up to a maximum of 15 3 Press Jto save the changes 4 Press Hto return to the Home screen Commissioning the MRLDS 450 1 Press Ithen and to enter the Network Summary screen 2 Highlight the MRLDS 450 to be commissione...

Page 4: ...st technical documentation and updates 3 If a box with Select Network appears on the screen select the MODBUS number where you configured the device either MODBUS 1 MODBUS 2 or MODBUS 3 and press 4 Select the address for the device and press Note The MODBUS address must be the same as the address assigned on the device Figure 4 Select MODBUS output Figure 5 Select Device Address ...

Page 5: ...t technical documentation and updates 5 A window will appear Press to continue 6 Press Jto save the assigned address 7 Press Hto return to the Home screen and press Ithen and to enter the Network Summary screen again 8 After a few seconds the MRLDS 450 should appear Online Figure 6 Set the Physical Address for the MRLDS 450 Figure 7 MRLDS 450 Network Summary Screen Online Status ...

Page 6: ...or its affiliates collectively Emerson reserves the right to modify the designs or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user Emerson is a trademark of Emerson Electric Co 202...

Reviews: