6
Integrate the meter with the control
system
Topics covered in this chapter:
•
•
Configure digital communications
6.1
Configure events
An event occurs when the real-time value of a user-specified process variable moves past a
user-defined setpoint. Events are used to provide notification of process changes or to
perform specific transmitter actions if a process change occurs.
6.1.1
Configure an enhanced event
ProLink III
Device Tools
>
Configuration
>
Events
>
Enhanced Events
Overview
An enhanced event is used to provide notification of process changes and, optionally, to
perform specific transmitter actions if the event occurs. An enhanced event occurs (is ON)
if the real-time value of a user-specified process variable moves above (HI) or below (LO) a
user-defined setpoint, or in range (IN) or out of range (OUT) with respect to two user-
defined setpoints. You can define up to five enhanced events.
Procedure
1.
Select the event that you want to configure.
2.
Specify
Event Type
.
Options
Description
HI
x
> A
The event occurs when the value of the assigned process variable (
x
) is
greater than the setpoint (
Setpoint A
), endpoint not included.
LO
x
< A
The event occurs when the value of the assigned process variable (
x
) is
less than the setpoint (
Setpoint A
), endpoint not included.
IN
A ≤
x
≤ B
The event occurs when the value of the assigned process variable (
x
) is
in
range,
that is, between
Setpoint A
and
Setpoint B
, endpoints included.
Integrate the meter with the control system
Configuration and Use Manual
45
Summary of Contents for Micro Motion LNG Series
Page 1: ...Configuration and Use Manual MMI 20032809 Rev AA February 2017 Micro Motion LNG Series Meters ...
Page 6: ...Contents iv Micro Motion LNG Series Meters ...
Page 8: ...Getting Started 2 Micro Motion LNG Series Meters ...
Page 12: ...Before you begin 6 Micro Motion LNG Series Meters ...
Page 18: ...Quick start 12 Micro Motion LNG Series Meters ...
Page 20: ...Configuration and commissioning 14 Micro Motion LNG Series Meters ...
Page 50: ...Configure device options and preferences 44 Micro Motion LNG Series Meters ...
Page 56: ...Integrate the meter with the control system 50 Micro Motion LNG Series Meters ...
Page 58: ...Complete the configuration 52 Micro Motion LNG Series Meters ...
Page 60: ...Operations maintenance and troubleshooting 54 Micro Motion LNG Series Meters ...
Page 74: ...Measurement support 68 Micro Motion LNG Series Meters ...
Page 94: ...Using ProLink III with the transmitter 88 Micro Motion LNG Series Meters ...
Page 98: ...Default values and ranges 92 Micro Motion LNG Series Meters ...
Page 99: ...Default values and ranges Configuration and Use Manual 93 ...