40
LF-Series Flowmeters: Sensor/Transmitter Installation
I/O Wiring – FM CIO Transmitters
Figure 7-15
Recommended pull-up resistor versus supply voltage – External power
7.6
Discrete input wiring
Discrete input wiring depends on whether you have configured terminals 5 and 6 (Channel C) for
internal or external power. The following diagrams are examples of proper wiring for these
configurations.
If external power is configured, power may be supplied by a PLC or other device, or by direct DC
input. See Table 7-2 for input voltage ranges.
Table 7-2
Input voltage ranges for external power
VDC
Range
3–30
High level
0–0.8
Low level
0.8–3
Undefined
4400
5
10
15
20
25
30
Supply voltage (volts
)
Ex
te
rn
al
p
u
ll
-up
r
e
si
st
or
r
a
nge
(o
hm
s
)
Recommended
resistor value range
400
600
800
4200
4000
3800
3600
3400
3200
3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000
Note: When using a discrete output to drive a relay, choose
external pull-up to limit current to less than 500 mA.
Summary of Contents for Micro Motion LF Series
Page 6: ...iv LF Series Flowmeters Sensor Transmitter Installation ...
Page 10: ...4 LF Series Flowmeters Sensor Transmitter Installation ...
Page 14: ...8 LF Series Flowmeters Sensor Transmitter Installation ...
Page 28: ...22 LF Series Flowmeters Sensor Transmitter Installation ...
Page 36: ...30 LF Series Flowmeters Sensor Transmitter Installation ...
Page 48: ...42 LF Series Flowmeters Sensor Transmitter Installation ...
Page 52: ...46 LF Series Flowmeters Sensor Transmitter Installation ...
Page 58: ...52 LF Series Flowmeters Sensor Transmitter Installation ...
Page 72: ...66 LF Series Flowmeters Sensor Transmitter Installation ...
Page 86: ...80 LF Series Flowmeters Sensor Transmitter Installation ...
Page 102: ...96 LF Series Flowmeters Sensor Transmitter Installation ...
Page 103: ......