7
Completing the configuration
Topics covered in this chapter:
•
Test or tune the system using sensor simulation
•
Back up transmitter configuration
•
Enable write-protection on the transmitter configuration
7.1
Test or tune the system using sensor
simulation
Use sensor simulation to test the system's response to a variety of process conditions,
including boundary conditions, problem conditions, or alarm conditions, or to tune the
loop.
Restriction
Sensor simulation is available only on flowmeters with the enhanced core processor.
Prerequisites
Before enabling sensor simulation, ensure that your process can tolerate the effects of the
simulated process values.
Procedure
1.
Navigate to the sensor simulation menu.
Communications tool
Menu path
Display
Not available
ProLink II
ProLink
>
Configuration
>
Sensor Simulation
ProLink III
Device Tools
>
Diagnostics
>
Testing
>
Sensor Simulation
Field Communicator
Service Tools
>
Simulate
>
Simulate Sensor
2.
Enable sensor simulation.
3.
For mass flow, set
Wave Form
as desired and enter the required values.
Option
Required values
Fixed
Fixed Value
Sawtooth
Period
Minimum
Maximum
Completing the configuration
Configuration and Use Manual
135
Summary of Contents for MICRO MOTION 2700
Page 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 373: ......