4.
Set
Parity
,
Stop Bits
, and
Baud Rate
as appropriate for your network.
5.
Set
Floating-Point Byte Order
to match the byte order used by your Modbus host.
Code
Byte order
0
1–2 3–4
1
3–4 1–2
2
2–1 4–3
3
4–3 2–1
for the bit structure of bytes 1, 2, 3, and 4.
Bit structure of floating-point bytes
Table 6-15:
Byte
Bits
Definition
1
SEEEEEEE
S=Sign
E=Exponent
2
EMMMMMMM
E=Exponent
M=Mantissa
3
MMMMMMMM
M=Mantissa
4
MMMMMMMM
M=Mantissa
6.
(Optional) Set
Additional Communications Response Delay
in “delay units.”
A delay unit is 2/3 of the time required to transmit one character, as calculated for
the port currently in use and the character transmission parameters. Valid values
range from 1 to 255.
Additional Communications Response Delay
is used to synchronize Modbus
communications with hosts that operate at a slower speed than the transmitter. The
value specified here will be added to each response the transmitter sends to the
host.
Tip
Do not set
Additional Communications Response Delay
unless required by your Modbus host.
6.6.4
Configure Digital Communications Fault Action
Display
Not available
ProLink II
ProLink
>
Configuration
>
Device
>
Digital Comm Settings
>
Digital Comm Fault Setting
ProLink III
Device Tools
>
Configuration
>
Fault Processing
Field Communicator
Configure
>
Alert Setup
>
I/O Fault Actions
>
Comm Fault Action
Integrate the meter with the control system
Configuration and Use Manual
131
Summary of Contents for MICRO MOTION 2700
Page 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 373: ......