128
Configuring and operating the system
UM6C55C (P7000597)
User Manual
Standard 10.00 (March 2008)
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
•
The “systemStatus” defines the highest alarm:
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning (lowest level of 'abnormal' status)
(4) minor
(5) major
(6) critical (highest level of 'abnormal' status)
(7) unmanaged
(8) restricted
(9) testing
(10) disabled
•
The “systemVoltage” defines the voltage of the power system in mV
including the sign.
•
The “systemCurrent” defines the current of the power system in mA
including the sign.
•
The “systemCapacity” defines the capacity used of the power system in
% of the total rectifier capacity.
SNMP trap
Figure 5.11 shows the list of the traps and the details of one trap.
Figure 5.11 – SNMP Trap
Under “alarmTrapEntry” shown in Figure 5.11, the alarm trap number, the
date and time, the alarm status, the alarm severity, the alarm description and
the alarm number are defined as follow:
•
The “alarmTrapNo” defines the unique sequence number of this alarm
trap.
•
The “alarmTime” defines the local date and local time when the alarm
occurs including the time zone.
•
The “alarmStatusChange” defines the type of alarm change:
(1) activated
(2) deactivated
Summary of Contents for Lorain CIP 48120 AP6C55CA
Page 2: ......