background image

4

2.

Remove the two setscrews from the top of the
motor coupler (Figure 1). Retain the setscrews for
future use.

3.

Route the two 80” motor leads through the center
hole in the motor cover. Place the motor cover over
the motor by aligning the reversing switch hole in
the cover over the reversing switch as shown in
Figure 2. Secure by installing three M5 x 10mm
pan head screws and three M5 external tooth
lockwashers (supplied) (Figure 2).

4.

Remove the hanger ball by loosening the setscrew
in the hanger ball until the ball falls freely down the
downrod (Figure 3). Remove the pin from the
downrod, then remove the hanger ball. Retain the
pin and hanger ball for reinstallation in Step 9.

5.

Separate, untwist and unkink the two motor leads,
then route them through the hanger ball/downrod
assembly and seat the downrod in the motor
coupler (Figure 4).

6.

Align the clevis pin holes in the downrod with the
holes in the motor coupler. Install the clevis pin and
secure with the hairpin clip (Figure 4). The clevis
pin must go through the holes in the motor coupler
It is critical that the clevis pin in the motor coupler is
properly installed and the setscrews securely
tightened. Failure to verify that the pin and
setscrews are properly installed could result in the
fan falling.

7.

Install two setscrews (previously removed in
Step 2) in the motor coupler (Figure 4). While
pulling up on the hanger ball, securely tighten both
setscrews.

MOTOR COVER

M5 EXTERNAL TOOTH 
LOCKWASHER (3)

M5 x 10mm PAN HEAD  
SCREW (3)

Figure 2

PIN

HANGER
BALL

SETSCREW

DOWNROD

Figure 3

Assembly Instructions

CAUTION: The blade assemblies must be
mounted on the motor assembly so that the
raised lip edge is facing up (Figure 1).

1.

Rotate the motor hub so the notched area is above
the screw hole in the motor hub. Install one blade
assembly on the top of the motor assembly using
two M6 x 12mm pan head screws and two M6
lockwashers (supplied) (Figure 1). Repeat this
procedure for the remaining two blade assemblies.

Electrical Requirements

If your fan is to replace an existing ceiling light fixture,
turn electricity off at the main fuse box at this time and
remove the existing light fixture.

Your new ceiling fan will require a grounded electrical
supply line of 120 volts AC, 60 Hz, 15 amp circuit.

The outlet box must be securely anchored and
capable of withstanding a load of at least 50 pounds.

To reduce the risk of fire, electric shock, or personal
injury, mount fan to outlet box marked “Acceptable
for Fan Support of 50 lbs. or less”, and use screws
supplied with outlet box. Most outlet boxes
commonly used for support of light fixtures are not
acceptable for fan support and may need to be
replaced. Consult a qualified electrician if in doubt.

WARNING

!

Turning off wall switch is not sufficient. To avoid
possible electrical shock, be sure electricity is turned
off at the main fuse box before wiring. All wiring must
be in accordance with National and Local codes and
the ceiling fan must be properly grounded as a
precaution against possible electrical shock.

WARNING

!

Figure 1

M6 x 12mm PAN HEAD 
SCREW

M6 LOCKWASHER

REMOVE 
SETSCREW (2)

REVERSING SWITCH

MOTOR ASSEMBLY

FLAT AREA OF 
MOTOR HUB

BLADE 
ASSEMBLY

U.L. Model No.: CF765

Summary of Contents for LOFT CF765BQ00

Page 1: ...STRUCTIONS Part No F40BP73780000 Form No BP7378 U L Model No CF765 60 Damp Location Ceiling Fan Owner s Manual CF765BQ00 Barbeque Black CF765BS00 Brushed Steel CF765WW00 Appliance White Model Numbers LOFT Net Weight 16 7 Lbs ...

Page 2: ...d may need to be replaced Consult a qualified electrician if in doubt 4 The downrod furnished with the fan proves the minimum recommended floor to fan blade clearance for an 8 foot ceiling 5 The fan must be mounted with the fan blades at least 7 feet from the floor to prevent accidental contact with the fan blades 6 Follow the recommended instructions for the proper method of wiring your ceiling f...

Page 3: ...edge or experience have your fan installed by a licensed electrician WARNING This Manual Is Designed to Make it as Easy as Possible for You to Assemble Install Operate and Maintain Your Ceiling Fan Installed Wire Length Wire Size A W G Up to 50 ft 14 50 100 ft 12 Unpacking Instructions For your convenience check off boxes are provided next to each step As each step is completed place a check mark ...

Page 4: ... Figure 2 PIN HANGER BALL SETSCREW DOWNROD Figure 3 Assembly Instructions CAUTION The blade assemblies must be mounted on the motor assembly so that the raised lip edge is facing up Figure 1 1 Rotate the motor hub so the notched area is above the screw hole in the motor hub Install one blade assembly on the top of the motor assembly using two M6 x 12mm pan head screws and two M6 lockwashers suppli...

Page 5: ... of the hanger ball Pull the hanger ball up tight against the pin and securely tighten the setscrew in the hanger ball Loose setscrews could create fan wobble MOTOR COVER CEILING COVER DOWNROD MOTOR COUPLING COVER Figure 5 1 Securely attach the hanger bracket to the outlet box using the two screws supplied with the outlet box Figure 8 FLOOR CEILING AT LEAST 7 Figure 7 The fan must be hung with at ...

Page 6: ...se and fan damage could result WARNING U L Model No CF765 To avoid possible electrical shock be sure electricity is turned off at the main fuse box before wiring NOTE If you are not sure if the outlet box is grounded contact a licensed electrician for advice as it must be grounded for safe operation WARNING How To Wire Your Ceiling Fan and Install the Control If you feel that you do not have enoug...

Page 7: ...tional Electrical Codes and all Local Codes Before starting disconnect power to the circuit at the fuse box or circuit breaker panel 7 Remove the faceplate and screws from the existing wall switch Pull switch out from wall outlet box 8 Disconnect wire from existing fan wall switch Figure 12 FACEPLATE SWITCH WALL OUTLET BOX Figure 12 9 Slide the Fan Control to the OFF position 0 10 Connect one BLAC...

Page 8: ...ounter Clockwise Down Winter Clockwise Up Maintenance IMPORTANT CARE INSTRUCTIONS for your Ceiling Fan Periodic cleaning of your new ceiling fan is the only maintenance that is needed When cleaning use only a soft brush or lint free cloth to avoid scratching the finish Abrasive cleaning agents are not required and should be avoided to prevent damage to finish Do not use water when cleaning your ce...

Page 9: ...e flanges not seated properly 4 Check to be sure the fan blade flanges seat firmly and uniformly to the surface of the motor If flanges are seated incorrectly loosen the flange screws and retighten according to the procedure in the section on How to Put Your Ceiling Fan Together 5 Hanger bracket and or ceiling outlet 5 Tighten the hanger bracket screws to the outlet box is not securely fastened bo...

Page 10: ...10 10 11 6 5 13 15 2 1 3 9 4 20 14 16 19 18 8 7 4 0 3 2 1 17 12 Repair Parts U L Model No CF765 ...

Page 11: ...alancing Kit 1 15 Cover Ceiling 763804 BQ 763804 BS 763804 WW 16 Cover Motor Coupling 763805 BQ 763805 BS 763805 WW 17 Housing Upper 763806 BQ 763806 BS 763806 WW 18 Harness Wiring 763811 763811 763811 19 Flange Blade Assembly set of 3 763808 BQ 763808 BS 763808 WW 20 SW46 Wall Control SW46 SW46 SW46 Owner s Manual BP7378 BP7378 BP7378 Before discarding packaging material be certain all parts have...

Page 12: ...tation charges to our factory or authorized service center Your Emerson Air Comfort Ceiling Fan should be properly packed to avoid damage in transit since we will not be responsible for any such damage What Is Not Covered The glass globes and light bulbs of your ceiling fan are not covered by this warranty This warranty also does not cover any defects malfunctions or failures caused by Repairs by ...

Reviews: