background image

3

Dimensions - Enclosures, I/O Expansion Module, Transformer Modules

Wiring Specifications

Front view

12"

(304.8mm)

14.25"

(361.95mm)

2.85"

(72.39mm)

Front view

18"

(457.2mm)

18"

(457.2mm)

2.85"

(72.39mm)

Top/bottom view

Top/bottom view

14"

(355.6mm)

3.83"

(97.2mm)

2.65"

(67.3mm)

Bottom view

Front view

LARGE ENCLOSURE 

SMALL ENCLOSURE &

I/O EXPANSION MODULE

TRANSFORMER MODULES

(115V & 230V)

Connection

Supported Wire Type

Maximum Wire Length

Rating

Digital

Input

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

750 ft. (225m)

Dry Contact

(24VDC, 10 mA)

Digital

Output

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

18 AWG* 

(recommended)

20 AWG

22 AWG

24VAC @3A

@3A 50 ft. (15m)

@2A 100 ft. (30m)

@1A 200 ft. (60m)

@3A 40 ft. (12m)

@2A 60 ft. (18m)

@1A 100 ft. (30m)

@3A 25 ft. (7m)

@2A 35 ft. (10m)

@1A 75 ft. (23m)

Analog Input

2-Wire 

Transducer

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

750 ft. (225m)

4-20 mA Signal

Input Selectable

Power Source 

(12/24VDC)

Analog Input

4-Wire 

Transducer

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 8489

Plenum - Belden 88489

750 ft. (225m)

4-20 mA Signal

Input Selectable

Power Source

(12/24VDC)

Common

Alarm

Output

18-22 AWG Stranded & Unshielded

18 AWG (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

18 AWG* 

(recommended)

20 AWG

22 AWG

24VAC @3A

@3A 50 ft. (15m)

@2A 100 ft. (30m)

@1A 200 ft. (60m)

@3A 40 ft. (12m)

@2A 60 ft. (18m)

@1A 100 ft. (30m)

@3A 25 ft. (7m)

@2A 35 ft. (10m)

@1A 75 ft. (23m)

Communication

RS232

Null Modem Cable

50 ft. (15m)

N/A

Communication

IGM422

SiteScan

18-22 AWG Stranded & Shielded

22 AWG (recommended)

Non Plenum - Belden 9461

Plenum - Belden 88761

1000 ft. (300m)

N/A

Communication

EIA485

18-22 AWG Stranded & Shielded

22 AWG (recommended)

Non Plenum - Belden 9461

Plenum - Belden 88761

3000 ft. (900m)

N/A

Phone/Modem

Line

4 Wire (Pins 3 & 4)

RJ11 Connector

N/A

N/A

24VAC Power

Connection

18-22 AWG Stranded & Shielded

18 AWG (recommended)

Non Plenum - Belden 8770

Plenum - Belden 88770

150 ft. (45m)

24VAC @1.3A

Power Connections (Transformer Module)

115VAC

14 AWG Stranded & Unshielded

Non Plenum - Belden 5101UE

150 ft. (45m)

115VAC @5A

230VAC

14 AWG Stranded & Unshielded

Non Plenum - Belden 5101UE

150 ft. (45m)

230VAC @0.5A

Summary of Contents for Liebert TM115

Page 1: ...niversal Monitor has a standard on board modem for remote monitoring via a telephone line The modem is preconfigured to work with the panel eliminating configuration and setup requirements Universal Monitor Two sizes of enclosures BAR CODE BAR CODE LIEBERT BATTERY LCD CONTRAST VBATT START TB7 24V INPUT P23 BATTERY 485 TOP BOTTOM TB10 COMMS 422 TB3 RELAY OUTPUTS TB2 CONTACT INPUTS ASS REV ON ON PFM...

Page 2: ...ice monitoring An integrated on board modem is included with each controller board for remote access to the Universal Monitor An RJ11 phone modem jack is also included The modem is factory configured eliminat ing field configuration and wiring requirements An IGM422 connection is included with each control ler to connect the Universal Monitor to Liebert s SiteScan Web Enterprise Monitoring System ...

Page 3: ...e Power Source 12 24VDC Analog Input 4 Wire Transducer 18 22 AWG Stranded Unshielded 18 AWG recommended Non Plenum Belden 8489 Plenum Belden 88489 750 ft 225m 4 20 mA Signal Input Selectable Power Source 12 24VDC Common Alarm Output 18 22 AWG Stranded Unshielded 18 AWG recommended Non Plenum Belden 9740 Plenum Belden 89740 18 AWG recommended 20 AWG 22 AWG 24VAC 3A 3A 50 ft 15m 2A 100 ft 30m 1A 200...

Page 4: ...04 F 0 C to 40 C 0 RH to 95 RH non condensing Modem Clock Specifics Modem Type Embedded 14 4K bps Clock Type Real Time Clock Clock battery backup type Lithium Cell non replaceable Clock battery life 7 years constant no power Modem battery backup type Nickel Cadmium replaceable Modem battery life 10 minutes at full load Communications Local EIA232 Remote Modem Baud rate 9600 bps Parity None Data bi...