Chapter 5 iCOM Controller 59
5.7.5 DIAGNOSTICS
The DIAGNOSTICS menu is classified into two groups. After entering the menu, pressing the up button and down
button can switch between two groups and pressing the enter button can enter the parameters of the corresponding
group. The parameters of group 1 are settable and used to help the maintenance personnel start and cut off devices
by hand in site, so as to realize the diagnosis for devices. The parameters of group 2 are read only and reflect the fault
condition of the devices. See Table 5-22 for detailed descriptions.
Table 5-22 Descriptions of DIAGNOSTICS parameters
Parameters Default
Setting
range
Description
S302
HP1 CODE
0
-
HP 1 alarm counting. The counter can be reset to 0 through
the parameter
S303
HP2 CODE
0
-
HP 2 alarm counting. The counter can be reset to 0 through
the parameter
S304
HT1 CNT
0
-
HT 1 alarm counting. The counter can be reset to 0 through
the parameter
S305
HT2 CNT
0
-
HT 2 alarm counting. The counter can be reset to 0 through
the parameter
S306
LP1 CODE
0
-
LP 1 alarm counting. The counter can be reset to 0 through
the parameter
S307
LP2 CODE
0
-
LP 2 alarm counting. The counter can be reset to 0 through
the parameter
S308
LP1 ACT
bar
-
Actual LP 1
S309
LP2 ACT
bar
-
Actual LP 2
S310
LP1 ACT
bar
-
Actual LP 1
S311
LP2 ACT
bar
-
Actual LP 2
S313
MANUAL
No
Yes, No
Selecting ‘Yes’ can turn on or off the components; selecting
‘No’ can prohibit manual setting
S314
MOTOR(S)
On
On, Off
Diagnosis switch of fan motor. The settings ‘On’ and ‘Off’ are
used to manually start and shut down the fan respectively
S315
COMP1
Off
On, Off
Diagnosis switch of compressor 1. The ‘On’ setting of this
parameter can start compressor 1 only when the fan has been
started
S315 C1
MODE Run
Run, Evac,
Charg
Compressor 1 operation mode selection
S316
C1 CAP
Off
On, Off
Refrigeration capacity output of digital scroll compressor 1
S317
C1 CYCLE
0%
-
-
S318
LLSV 1
Off
On, Off
Diagnostic of liquid line solenoid valve of compressor 1
S319 COMP2
Off
On,
Off
Diagnostic swtich of compressor 2. Note that the On setting of
this parameter can start compressor 2 only when the fan has
been started
S319 C2
MODE Run
Run, Evac,
Charg
Compressor 2 operation mode selection
S320
C2 CAP
Off
-
Refrigeration capacity output of digital scroll compressor 2
S321 C2
CYCLE 0%
-
-
S322
LLSV2
Off
On, Off
Diagnosis switch of liquid line solenoid valve of compressor 2
S324 EL
HEAT1 Off
On,
Off.
Diagnosis switch of electric heater 1. The ‘On’ setting of this
parameter can start electric heater 1 only when the air loss is
normal
S325 EL
HEAT2
Off
On,
Off.
Diagnosis switch of electric heater 2. The ‘On’ setting of this
parameter can start electric heater 2 only when the air loss is
normal
S326
EL HEAT3
Off
On, Off.
Diagnosis switch of electric heater 3. The ‘On’ setting of this
parameter can start electric heater 3 only when the air loss is
normal
S327
SCR HEAT
-
0 ~ 100 %
SCR Heat
S328
DEHUMl
Off
On, Off
Diagnostic switch of Dehumidification solenoid valve
S329
HUM FILL
Off
On, Off
Diagnosis switch of solenoid valve of water supply to the
humidifier
Group 1
S330
HUM
Off
On, Off
Diagnosis switch of humidifier. The ‘On’ setting of this
parameter can start the humidifier only when the air loss is
normal
Liebert.PEX2 Series Air Conditioner User Manual