Emerson Liebert NXC 10-20kVA Connection Manual Download Page 2

1.2 Connection Cables For Dry Contact Port 

The UPS provides five dry contact ports; see Figure 1-1 for  the specific positions. The silk prints of the five dry 
contact ports are 1, 2, 3, 4 and 5. The pin layout of each dry contact port is shown in Figure 1-3, and the port 
description is shown in Table 

+12V

+12V

+12V

SA

L

A

R

M

GN

D

O

n_bat

ter

y

GN

D

O

n_bapas

s

GN

D

E

po_N

C

+12V

+12V

Epo_I

N

BFP

_

o

BFP_s

BFP_c

Dry contact port1       

 

Dry contact port

 

  Dry contact port

 3       

Dry contact port 4 

Dry contact port 5 

Table 1-1 

Description of the dry contact ports 

Silk print 

Port name 

Pin NO. 

Pin name 

Meaning 

Output port of alarm 

1.1 

S_ALARM 

The signal level is 12V when the system alarms 

1.2

GND 

GND

Output port of battery status 

2.1 

ON_BATTERY  The signal level is 12V when the system runs in battery mode 

2.2

GND 

GND

Output port of bypass status 

3.1 

ON_BYPASS 

The level is 12V when the system runs in bypass mode 

3.2

GND 

GND

Input port of remote EPO* 

4.1 

EPO_NC 

EPO activated when opened to 4.2 

4.2 

12V 

EPO activated when opened to 4.1 

4.3 

12V 

EPO activated when shorted to 4.4 

4.4 

EPO_IN 

EPO activated when shorted to 4.3 

Output port of bypass 
backfeed 

5.1

BFP_O

Bypass backfeed protection relay (normally open). Closes when 

 

short circuit of bypass silicon controlled rectifier (SCR) leads to 
backfeed 

5.2 

BFP_S 

The middle point of the bypass backfeed protection relay 

5.3

BFP_C

Bypass backfeed protection relay (normally open). Opens 
when short circuit of bypass SCR leads to backfeed 

Note*: 
Pin1 and pin2, or pin3 and pin4 of the dry contact port 4 reserves the corresponding terminals for configuring the REPO function. The 
REPO device also needs the shielded cable to connect to the normally open/closed remote REPO switch between the two terminals. If not 
necessary, you should disconnect pin3 and pin4 of the dry contact port 4, or short pin1 and pin2 of the dry contact port 4. Pin1 and pin2 of 
the dry contact port 4 have been shorted before delivery 

Note 

The EPO action of the UPS will stop the rectifier, inverter and static bypass, but it cannot disconnect the UPS mains input inside. If you want 
to disconnect the UPS completely, just disconnect the upstream input MCB when generating the EPO.   

Figure 1

3  Pin layout of dry contact ports 