background image

1

I

MPORTANT

 S

AFETY

 I

NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important safety and operating instructions concerning the installation and 

operation of the Liebert NX Remote Monitoring Panel (RMP). Read all safety, installation and operat-

ing instructions before beginning installation. Adhere to all warnings on the unit and in this manual. 

Follow all operating and user instructions.
The Liebert NX Remote Monitoring Panel must be commissioned and serviced by an engineer 

approved by Liebert. Failure to do so may result in personnel safety risk, equipment malfunction and 

invalidation of warranty.
The Remote Monitoring Panel is designed and intended for commercial and industrial use. It is not 

recommended for use in life-support applications.

ELECTROMAGNETIC COMPATIBILITY

—This is a low-emission, Class A product. Operating 

this device in a residential area is likely to cause harmful interference that users must correct at their 

own expense. Pursuant to FCC regulations, operation is subject to the following two conditions:
1. This device may not cause harmful interference; and
2. This device must accept any interference received, including interference that may cause 

undesired operation.

Conformity and Standards

This equipment complies with CE directives 73/23 & 93/68 (LV Safety) and 89/336 (EMC), with Aus-

tralia and New Zealand EMC Framework (C-Tick) and with the following product standards for Unin-

terruptible Power System (UPS).

• EN / IEC / AS 62040-1-1-General and safety requirements for use in operator access area
• EN / IEC / AS 62040-2-EMC requirements; Class A compliant
• EN / IEC / AS 62040-3-Performance requirements and test methods

This equipment complies with 

UL 60950-1:2003, First Edition CSA C22.2 No. 60950-1-03 1st Ed.

 

April 1, 2003.
For details, see 

4.0 - Technical Specifications

.

Continued compliance requires installation in accordance with these instructions and the use of man-

ufacturer approved accessories only.

General

The unit must be grounded in accordance with applicable current local electrical regulations.
As with other types of power equipment, dangerous voltages are present within the RMP enclosure. 

The risk of contact with these voltages is minimized as the live component parts are housed behind a 

hinged, lockable door. No risk exists to any personnel when operating the equipment in the normal 

manner, following the recommended operating procedures. 
All equipment maintenance and servicing procedures involve internal access and should be carried 

out only by trained personnel.

User-Serviceable Parts

There are no user-serviceable parts behind covers requiring a tool for removal. All equipment mainte-

nance and servicing procedures involving internal access requires the use of a tool and should be car-

ried out only by trained personnel.

I

NFORMATION

 

FOR

 

THE

 P

ROTECTION

 

OF

 

THE

 E

NVIRONMENT

Unit Servicing

This unit makes use of components dangerous for the environment, including electronic cards and 

other electronic components. Any of these components that are removed from the unit must be taken 

to specialized collection and disposal centers.

Unit Dismantling

If this unit must be dismantled, this operation must be carried out only by properly trained and qual-

ified specialized personnel. The unit must be taken to a center that specializes in collection and dis-

posal of dangerous substances.

Summary of Contents for Liebert NX Remote Monitoring Panel

Page 1: ... F3 F2 F1 EMERSON Network Power Liebert Press any key back to main menu Liebert NX 081 kVA 3x3 12 16 2009 Single 12 22 14 Normal STATUS EMERSON Network Power SILENCE ON OFF Remote Monitor Panel Lie be rt N X Liebert Remote Monitoring Panel User Manual ...

Page 2: ......

Page 3: ...the RMP on Drywall 5 2 6 Electrical connections 6 3 0 OPERATION 8 3 1 Startup and Reset 8 3 2 LED Mimic Power Flow 11 3 3 Audible Alarms Buzzer 11 3 4 Direct Access Push Buttons Keys 12 3 5 LCD Monitor and Menu Keys 12 3 6 Detailed Description of Menu Items 14 3 7 Status and Event Messages 16 3 8 Prompt Popup Windows 20 3 9 Dynamic Energy Flow Chart and UPS Help Screen 20 3 10 Default screen saver...

Page 4: ...een 21 Figure 17 Default screen 21 TABLES Table 1 RMP component location in Figure 1 3 Table 2 Communication cable specifications 4 Table 3 Rectifier indicator 11 Table 4 Battery indicator 11 Table 5 Bypass indicator 11 Table 6 Inverter indicator 11 Table 7 Load indicator 11 Table 8 Status Alarm indicator 11 Table 9 Audible alarm key 11 Table 10 Menu key Icons and their meaning 12 Table 11 UPS sys...

Page 5: ... Class A compliant EN IEC AS 62040 3 Performance requirements and test methods This equipment complies with UL 60950 1 2003 First Edition CSA C22 2 No 60950 1 03 1st Ed April 1 2003 For details see 4 0 Technical Specifications Continued compliance requires installation in accordance with these instructions and the use of man ufacturer approved accessories only General The unit must be grounded in ...

Page 6: ...ty and maintenance staff This type location enhances the unit s capacity to provide notice if a status change or alarm requires an electrician or a UPS technician s intervention The RMP can monitor only one Liebert NX UPS If there are multiple Liebert NX UPSs an RMP will need to be installed for each unit For parallel systems the system load information may be viewed via the system screen from any...

Page 7: ... update 6 Audible Alarm Buzzer 15 RS 232 Reserved not used 7 UPS Status and Alarm indicator 16 AC power input cable entry 8 F1 Function Key 17 RS 485 communication cable entry 9 F2 Function Key UPS Room Liebert NX Communication Cable Maxi mum Length 100m 328ft field supplied Maintenance or Control Room HELP F4 F3 F2 F1 EMERSON Network Power Liebert Press any key back to main menu Liebert NX 081 kV...

Page 8: ...ntilation to keep the temperature within the specified operating range see Table 17 If the RMP is to be installed on a wall or other vertical surface ensure that the surface can bear the weight see Table 16 and there is no water leakage 2 3 Power Supply The RMP requires a 120V 230V AC input for detailed electrical specifications see Table 18 Figure 3 RMP electrical input plug 2 4 Cable Specificati...

Page 9: ...hor and tighten firmly 4 Remove the four hooks from the RMP reverse them then reattach them to the RMP 5 Hang the RMP on the wall by slipping the hooks over the heads of the screws and lowering the RMP slowly until the screws are seated in the slotted portion of the hooks Figure 5 Mounting hole dimensions UPS_U2_J24 Up to 328ft 100m RMP_X1_J1 Shield Shield 485 485 485 485 1 2 3 4 1 2 3 4 STATUS Re...

Page 10: ...Figure 6 Figure 6 Power and communication cable routing Extract four screws to remove the cable access cover Attach AC Input cable to labeled connector Attach communi cation cable to labeled RS 485 connector Reinstall cable access cover inserting AC Input and communication cables into respective labeled slots ...

Page 11: ...bert NX as shown in Figure 7 Figure 7 RS 485 cable connection to Liebert NX Connect the other end of the RS 485 signal cable to the X4 slot on the monitor board The monitor board is inside the UPS front door Communication connections on Remote Monitoring Panel board ...

Page 12: ... Figure 9 will be displayed while the data is loading The loading time is about 30 seconds Figure 9 Data loading progress screen If the firmware in the UPS and the RMP are compatible the RMP will display the screen shown in Figure 10 The NX screen will display the same screen F2 F4 F5 F1 F3 Liebert NX 2006 01 22 12 30 36 30kVA 3X3 Unit 1 Normal Bypass Main Vphase V Iphase A Freq Hz Vline V P F A A...

Page 13: ...tor 50 50 50 1 4 1 4 1 4 F2 F4 HELP F1 F3 Input breaker closed 01 12 12 28 16 Manual turn on 01 12 12 30 06 UPS in normal mode 01 22 12 30 16 Liebert NX 2006 01 22 12 30 36 30kVA 3X3 Unit 1 Normal Bypass Main Vphase V Iphase A Freq Hz Vline V P F A AB 120 20 5 50 1 208 0 99 B BC 120 20 5 50 1 208 0 99 C CA 120 20 5 50 1 208 0 99 Output Remote Monitor Panel silence F2 F4 HELP F1 F3 Input breaker cl...

Page 14: ...t NX 2006 01 22 12 30 36 30kVA 3X3 Unit 1 Normal Bypass Main Vphase V Iphase A Freq Hz Vline V P F A AB 120 20 5 50 1 208 0 99 B BC 120 20 5 50 1 208 0 99 C CA 120 20 5 50 1 208 0 99 Output Communication with UPS Failed CommErrID 0x01 F2 F4 HELP F1 F3 Input breaker closed 01 12 12 28 16 Manual turn on 01 12 12 30 06 UPS in normal mode 01 22 12 30 16 Liebert NX 2006 01 22 12 30 36 30kVA 3X3 Unit 1 ...

Page 15: ...rmal Failed overcurrent overtemperature Off Battery and Converter Normal Battery charging Table 5 Bypass indicator Green Load on Bypass power Red Bypass not available out of normal range or Static bypass switch fault Off Bypass Normal load not on bypass Table 6 Inverter indicator Green Inverter Normal and powering the load Flashing Green Inverter ON starting up synchronizing or standing by ECO mod...

Page 16: ...avigate within the graphic LCD monitor windows Figure 14 Graphic LCD monitor windows and keypad The function of keys F1 to F4 is shown by a self explanatory icon as appropriate for the particular window As shown in Figure 14 above pressing F1 moves the cursor resting in OUTPUT from the UPS Menu Window 2 to current record window 4 where it would first rest in Input breaker closed In a similar manne...

Page 17: ... No 1 Phone No 2 Phone No 3 Command password System Sout kVA Pout kW Qout kVAR Single unit no parallel data Records history log Language Choices for display Mains input L N voltage V L N current A Frequency Hz L L voltage V Power factor Load Sout kVA Pout kW Qout kVAR Loadlevel Crest factor Bypass L N voltage V Frequency Hz L L voltage V Output L N voltage V L N current A Frequency Hz L L voltage ...

Page 18: ...Warning or Fault Normal UPS operating Normal Warning System attention required e g AC Input Failure Fault UPS Fuse or Hardware Failure Table 12 Descriptions of RMP menus and data window items Menu Type Item Type Explanation Mains input L N voltage V Phase voltage L N current A Phase current Frequency Hz Input frequency L L voltage v Line line voltage Power factor Power factor TX Input L N voltage ...

Page 19: ...on Phone No 1 When IntelliSlot 1 Communication mode is Modem this is the first phone number to be dialed to send an alarm notification Phone No 2 When IntelliSlot 1 Communication mode is Modem this is the second phone number to be dialed to send an alarm notification Phone No 3 When IntelliSlot 1 Communication mode is Modem this is the third phone number to be dialed to send an alarm notification ...

Page 20: ...ecover automatically Check the environment and ventilation Batt Contactor Fail Battery contactor or circuit breaker not responding to control signals Batt Charger Fault The voltage of the battery charger is too high Control Power 1 Fail UPS operates but Redundant Control Power is not available Mains Phase Reversed AC Input phase sequence is reversed Rectifier Overcurrent Rectifier is overloaded So...

Page 21: ...ce the overload condition is removed 1 Confirm that the alarm is true by checking the load percent indicated on the LCD panel to determine which phase is being overloaded 2 If the alarm is true measure the actual output current to verify that the indications are valid Disconnect unnecessary load and ensure the safety In a parallel system a severe load sharing error can also leads to the alarm Syst...

Page 22: ... above 135 rating The UPS just alarms and does nothing LBS Active Load Bus Synchronization is active The UPS is acting as an LBS master or slave in a dual bus configuration Setting Save Error History records not saved Reserved Mains Neutral Lost AC Input mains reference neutral not detected Protocol version clash Firmware incompatibility between Monitor Board and Digital Signal Processor Board Bat...

Page 23: ... Input Isolation Transformer Over Temperature Ext Output TX Overtemp External Output Isolation Transformer Over Temperature Battery Room Alarm Environment in Battery Room Needs Attention Rotary Sw Test Pos Rotary switch is in test position Rotary Sw Normal Pos Rotary switch is in normal position Rotary Sw Bypass Pos Rotary switch is in bypass position Rotary Sw Maint Pos Rotary switch is in mainte...

Page 24: ...peration leads to inverter overload confirm or cancel The turn off this inverter will lead to the overload of remaining inverter s in a parallel system Turn on more UPS to carry current load The number of paralleled inverters already turned on is insufficient to carry the existing load Battery will be depleted confirm Battery Capacity test discharges the battery 100 System self test finished every...

Page 25: ...2 minutes of inactivity the backlight turns off Press any key F1 F4 or Help to reactivate the screen Figure 17 Default screen F2 F4 HELP F1 F3 Help information Select the previous menu item Select the current record window Q3 Q2 Q1 Q5 Press help key back to main menu F2 F3 F4 HELP F1 Liebert NX 2005 05 22 12 30 36 20 kVA 3x3 UNIT 1 NORMAL Press any key back to main menu ...

Page 26: ...40 Relative humidity 90 or less at 20 C Acoustical noise dBA 32 Altitude of operation m 2000 Storage transport temperature C 25 70 Table 18 Electrical specifications Electrical Characteristics Units Value Rated input voltage VAC 100 120 220 230 240 Input voltage range VAC 90 254 Input Frequency Hz 50 60 Input frequency tolerance Hz 47 67 Input Current A 0 7A Max Table 19 Cable specifications Item ...

Page 27: ...ted RFI CISPR 22 A Radiated RFI CISPR 22 A Table 21 Electromagnetic susceptibility EMS immunity levels Standard IEC EN AS Requirement Level Criterion Electrostatic Discharge 61000 4 2 6 kV contact 8 kV air 3 B Radiated Electric Fields 61000 4 3 10 V m 3 A Fast Electrical Transients 61000 4 4 2 kV 5 kHz Power and Signal ports 3 B Surges 61000 4 5 Power port 2kV common mode 1kV differential mode Sig...

Page 28: ...oration All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring 800 222 5877 Liebert monitoring emerson com Outside the US 614 841 6755 Single Phase UPS 800 222 5877 upstech emersonnetworkpower com Outside the US 614 841 6755 Three Phase UPS 800 543 2378 powertech emersonnetworkpower com Environmental Sy...

Reviews: