Operator Control Panel and Display
102
Auto start
After UPS was shutdown at EOD, inverter auto starts when utility restore
REC FLASH UPDATE
Rectifier firmware is being updated
INV FLASH UPDATE
Inverter firmware is being updated
MONITOR FLASH UPDATE
Monitor firmware is being updated
Input contactor fault
Input contactor fault
Contactor P.S. 1 fault
Contactor Power Supply board 1 Fault
Contactor P.S. 2 fault
Contactor Power Supply board 2 Fault
LBS abnormal
LBS is abnormal
DSP firmware error
The inverter firmware does not match with the rectifier firmware.
Input Fuse
Fail Internal AC Input Fuse to Rectifier Failed. Rectifier shuts down. Battery
discharges. Not applicable for 30-40kVA models.
Input Disconnect Open
AC mains input power switch open
Input Disconnect Closed
AC mains input power switch closed
Maint. Disconnect Open
Maintenance bypass power switch open
Maint. Disconnect Closed
Maintenance bypass power switch closed
Bypass Disconnect Open
AC bypass input power switch open
Bypass Disconnect Closed
AC bypass input power switch closed
Output Disconnect Open
UPS Output power switch open
Output Disconnect closed
UPS Output power switch closed
Input Inductor Overtemp.
Overheating of Rectifier input filter choke. Rectifier shuts down. Battery discharges.
Balancer Fault
Internal VDC(+) and VDC(-) off-set by over 50V exceeding the Inverter DC offset
compensation capacity. Inverter shuts down. Load transfers to bypass.
Balancer Over Current
Internal Inverter DC off-set balancing IGBT current rating exceeded 300%. Inverter
shuts down. Load transfers to bypass.
Balancer overtemp.
Inverter voltage offset control choke overheated. Inverter shuts down. Load
transfers to bypass.
Inv. Inductor Overtemp.
Inverter output filter choke overheated. Inverter shuts down. Load transfers to
bypass.
Batt. Converter Fault
Battery converter output voltage beyond limits or battery fuse failed. Battery
converter shuts down. Battety backup not available.
Batt. Conv. Over. Curr.
Battery converter overloaded. Battery converter shuts down. Battery backup not
available.
Batt. Converter Overtemp.
Overheating of Battery converter heatsinks. Battery converter shuts down. Battery
backup not available.
Output Disabled
UPS Output Disabled (test mode)
Table 23
UPS messages
Message
Description / Suggested Action (if any)