28 Wiring Inspection
10.0 W
IRING
I
NSPECTION
9HULI\DOOSRZHUFRQQHFWLRQVDUHWLJKW
9HULI\DOOFRQWUROZLUHWHUPLQDWLRQVDUHWLJKW
9HULI\DOOSRZHUZLUHVDQGFRQQHFWLRQVKDYHSURSHUVSDFLQJEHWZHHQH[SRVHGVXUIDFHVSKDVHWR
SKDVHDQGSKDVHWRJURXQG
9HULI\WKDWDOOFRQWUROZLUHVDUHUXQLQLQGLYLGXDOVHSDUDWHVWHHOFRQGXLW
Table 1
Power Wiring Terminals - Factory Supplied
UPS Module Rating
Connection Type
30-130 kVA
Bus bars. See Outline Drawings for dimensions.
Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 (see Table 3 of this
manual) and associated notes of the National Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Connect wire to
the lug using tools and procedures specified by the lug manufacturer.
Table 2
Torque Specifications
Nut and Bolt Combinations
Bolt Shaft Size
Grade 2
Standard
Electrical Connections
with Belleville Washers
Lb-in
N-m
Lb-in
N-m
1/4
53
6.0
46
5.2
5/16
107
12
60
6.8
3/8
192
22
95
11
1/2
428
48
256
29
Circuit Breakers With Compression Lugs (For Power Wiring)
Cable Size or Range
Lb-in
N-m
#6 - #4
100
11
#3 - #1
125
14
1/0 - 2/0
150
17
3/0 - 200 MCM
200
23
250 - 400 MCM
250
28
500 - 700 MCM
300
34
Terminal Block Compression Lugs (For Control Wiring)
AWG Wire Size or Range
Lb-in
N-m
#22 - #14
3.5 to 5.3
0.4 to 0.6
Use the values in this table unless the equipment is labeled with a
different torque value.
Summary of Contents for Liebert Npower 100-130 kVA
Page 4: ...DISCONTINUED PRODUCT ...
Page 5: ...DISCONTINUED PRODUCT i Table of Contents ...
Page 6: ...DISCONTINUED PRODUCT ...
Page 7: ...DISCONTINUED PRODUCT iii List of Figures ...
Page 8: ...DISCONTINUED PRODUCT ...
Page 10: ...DISCONTINUED PRODUCT ...
Page 12: ...DISCONTINUED PRODUCT 2 Installation Considerations 2 0 INSTALLATION CONSIDERATIONS ...
Page 20: ...DISCONTINUED PRODUCT 10 Battery Installation ...
Page 21: ...DISCONTINUED PRODUCT Battery Installation 11 6 2 Matching Battery Cabinets ...
Page 22: ...DISCONTINUED PRODUCT 12 Battery Installation 6 3 Non Standard Batteries ...
Page 32: ...DISCONTINUED PRODUCT 22 Wiring Considerations 8 0 WIRING CONSIDERATIONS ...
Page 33: ...DISCONTINUED PRODUCT Wiring Considerations 23 8 1 Power Wiring ...
Page 34: ...DISCONTINUED PRODUCT 24 Wiring Considerations 8 2 Control Wiring ...
Page 41: ...DISCONTINUED PRODUCT Installation Drawings 31 Figure 12 Outline Drawing 65 80 kVA UPS ...
Page 42: ...DISCONTINUED PRODUCT 32 Installation Drawings Figure 13 Outline Drawing 100 130 kVA UPS ...
Page 65: ...DISCONTINUED PRODUCT Installation Drawings 55 Figure 36 Outline Drawing LBS Control Panel ...
Page 67: ...DISCONTINUED PRODUCT Installation Drawings 57 Figure 38 Outline Drawing LBS Transformer Panel ...
Page 70: ...DISCONTINUED PRODUCT 60 Installation Drawings Figure 41 Control Wiring 30 130 kVA UPS ...
Page 76: ...DISCONTINUED PRODUCT 66 Installation Drawings Figure 47 Control Wiring Site Scan Interface ...
Page 79: ...DISCONTINUED PRODUCT Installation Drawings 69 Figure 50 Control Wiring NIC Option ...
Page 80: ...DISCONTINUED PRODUCT 70 Installation Drawings Figure 51 Control Wiring Power Supply Option ...
Page 81: ...DISCONTINUED PRODUCT Installation Drawings 71 Figure 52 Control Wiring Internal Modem Option ...
Page 84: ...DISCONTINUED PRODUCT 74 Installation Drawings Figure 55 Control Connection Diagram 50 130 kVA ...
Page 86: ...DISCONTINUED PRODUCT 76 Installation Drawings Figure 57 Terminal Details 30 50 kVA UPS ...
Page 87: ...DISCONTINUED PRODUCT Installation Drawings 77 Figure 58 Terminal Details 65 80 kVA UPS ...
Page 88: ...DISCONTINUED PRODUCT 78 Installation Drawings Figure 59 Terminal Details 100 130 kVA UPS ...
Page 98: ...DISCONTINUED PRODUCT 88 ...
Page 99: ...DISCONTINUED PRODUCT ...