Customer Wiring

Specifications

Wiring Specifications

Power 

Requirements

AC Inputs

18 - 24 VAC; 50/60 Hz

DC Inputs

12 - 36VDC

Power Consumption

6VA maximum

Dimensions - W x D x H: in. (mm)

7 x 4 x 1.5 (178 x 102 x 38)

Weight

Net - oz. (kg)

7 (0.2)

Shipping - lb. (kg)

1.3 (0.6)

Ambient Operating Environment, °F (°C)

32 to 104 (0 to 40); 10% to 90% RH (non-condensing)

Ambient Storage Temperature, °F (°C)

-4 to 140 (-20 to 60)

Protection

SELV Isolated User Connections, Watchdog Timer Circuitry

Communication

Ports

Service Terminal (RS-232)

DB9F, DTE

Unit Input 

Communications

TB1, 2-Position Terminal Block

P1, 20-PIN Vertical Header with Ejection Latches (for some UPS models)

Modbus (RS-485)

TB2, 2-Position Terminal Block

Ethernet Communications

RJ45

Connection

Supported Wire Types

Maximum Wire Length

TB1 (RS-422)

18-22 AWG Stranded & Shielded; 

18 AWG* recommended

Non Plenum - Belden 9461; Plenum - Belden 88761

1000 ft. (300m)

TB2 (RS-485)

18-22 AWG Stranded & Shielded; 

18 AWG* recommended

Non Plenum - Belden 9461; Plenum - Belden 88761

3000 ft. (915m)

TB3 (Power Input)

18-22 AWG Stranded & Shielded; 

18 AWG* recommended

Non Plenum - Belden 8770; Plenum - Belden 88770

20 ft. (6m)

DB9F Connector

DTE Null Modem Cable

50 ft. (15m)

RJ45 Connector

Standard Category 5 Cable

328 ft. (100m)

Input power 

(input to TB3)

Pin 1(+)

Pin 2(-)

Pin 3 (NC)

Network port

for NMS and

Web access

DTE serial port 

for configuration 

(requires null-modem 

connection)

IGMnet or Liebert SiteScan

®

 Comms 

from unit (input to TB1 or P1)

Refer to user manual for details

Modbus output

for BMS

(output from TB2)

TB1: Pin 1 (+), Pin 2 (-)

TB2: Pin 1 (+), Pin 2 (-)