User Menu Parameters
95
Liebert
®
iCOM
®
for Liebert DSE
™
U206 Low Return Humidity
—Allows a user to adjust the point at which the actual return
humidity activates a Low Humidity Alarm. This parameter is adjustable from 1% to 99%. The default
setting is 40%F.
U207 Sensor A Alarms
—Enables or disables the alarms for reference Sensor A. When enabled, the
Sensor A temperature and humidity values will be compared to a high and low setting.
U208 High Temperature Sensor A
—Allows a user to adjust the point at which the actual Sensor A
temperature activates a High Temperature Alarm. This parameter is adjustable from 34°F to 210°F.
The default setting is 80°F.
U209 Low Temperature Sensor A
—Allows a user to adjust the point at which the actual Sensor A
temperature activates a Low Temperature Alarm. This parameter is adjustable from 34°F to 210°F.
The default setting is 65°F.
U210 High Humidity Sensor A
—Allows a user to adjust the point at which the actual Sensor A
humidity activates a High Humidity Alarm. This parameter is adjustable from 1% to 99%. The
default setting is 60%F.
U211 Low Humidity Sensor A
—Allows a user to adjust the point at which the actual Sensor A
humidity activates a Low Humidity Alarm. This parameter is adjustable from 1% to 99%. The default
setting is 40%F.
Figure 69 Set alarms screen, page 2
U213 Supply Sensor Alarms
—Enables or disables the supply sensor alarms. When enabled, the
supply temperature and humidity values will be compared to a high and low setting.
U214 High Supply Temperature
—Sets the temperature at which the High Supply Temperature
Alarm is activated. This parameter is adjustable from 34°F to 210°F. The default setting is 75°F.
U215 Low Supply Temperature
—Sets the temperature at which the Low Supply Temperature
Alarm is
U21
activated. This parameter is adjustable from 34°F to 210°F. The default setting is 50°F.
U219 Remote Sensor Alarms
—Enables or disables the Remote sensor alarms. When enabled, the
Remote temperature values will be compared to a high and low setting.
U220 High/Low Remote Temperature
—Enables or disables remote air alarm. When enabled, the
high and low temperature alarm will allow a user to adjust the point at which the actual remote
temperature activates a Low Remote Temperature Alarm. This parameter is used when common
alarm points will be shared by all sensors. Otherwise, the remote sensors can be set individually on
page 3. This parameter is adjustable from 34°F to 210°F. The default setting 50°F.
U221 Separate thresholds are on page 3—
Informational