UPS System: HIPULSE E
Communication System Manual
Description of Protocol
(Modbus/Jbus Interface)
Page 5-2
(04/07)
5.2
Hardware features of Communication Protocol
Speed
1200/2400/4800/9600 Baud
Start Bits
1
Data Bits
8
Stop Bits
1 or 2
Parity Bits
1 or 2
Parameter
Description
Parity bit
1 or 2 = [1= None 2 = Even]
5.3
Software Features of Communication Protocol :
The Panel board acts as a Slave, meaning that it stays on standby awaiting commands coming in from the BMS.
Note:
Use of the MODBUS/JBUS RTU
excludes
the “connection with UPS network” function in which a Master Panel
queries panels of Slave units and permits communication with a Local/Remote PC; in the MODBUS/JBUS RTU
protocol none of the panels is given Master status and none of the UPS panels may communicate with the
Local/Remote PC.