Using the configuration program, the user may specify the number of external battery cabinets
attached to the UPS. The factory default is programmed for internal batteries only.
Table 21
shows the estimated run times at different loads.
Internal Battery
+ 4 External
Battery Cabinets
10%
454
442
463
447
456
20%
323
300
340
310
420
30%
194
161
218
165
304
40%
153
138
164
144
200
50%
134
110
147
122
160
60%
110
92
130
99
145
70%
95
74
109
79
130
80%
77
62
96
68
111
90%
67
50
79
53
102
100%
53
46
71
49
93
Internal Battery
+ 5 External
Battery Cabinets
10%
464
454
480
459
466
20%
343
324
429
332
430
30%
224
194
316
206
332
40%
166
153
203
158
225
50%
150
134
161
140
195
60%
134
110
147
122
161
70%
112
95
133
102
149
80%
100
77
113
82
137
90%
82
67
102
73
126
100%
74
53
91
64
110
Internal Battery
+ 6 External
Battery Cabinets
10%
480
463
480
467
480
20%
430
341
442
420
452
30%
317
219
334
301
423
40%
204
164
227
183
321
50%
162
148
191
153
227
60%
148
131
159
138
195
70%
134
110
147
122
162
80%
120
97
135
104
152
90%
103
80
122
92
142
100%
92
71
107
77
133
Run times in this table are approximate. They are based on new, fully charged standard battery modules at a temperature of 77°F (25°C)
with 100% resistive UPS loading. Run times listed above can vary by ±5% due to manufacturing variances of the individual batteries.
Table 21
Battery run time, minutes
Number of External
Battery Cabinets
Load Percent
of Capacity
208/120 VAC RT Models
208 VAC RT Model
5 kVA
6 kVA
8 kVA
10 kVA
6 kVA (L630)