A prompt screen is displayed during the operation of the system to alert you to certain conditions and/or to
require your confirmation of a command or other operation. See
for the prompts and meanings.
3.4.5
Warning List
All UPS warning messages are described in
Table 3-3
System prompts and meanings
Prompt
Meanings
Mains Power Restored
The mains power returns and the UPS transfers back to mains (AC)
mode.
UPS Return From A Low Battery Condition
The UPS transfers back to mains (AC) mode from battery low mode.
UPS Return From Battery Mode
The UPS transfers back to mains (AC) mode from battery mode.
UPS Self Test Successful
The UPS self-test is successfully performed.
UPS Shutdown Command Received
The UPS shut down was initiated through communication.
UPS Turn Off
The UPS shuts down and has no output power.
UPS Turn On
The UPS starts up successfully and supplies protected power to the
load.
UPS Shutdown Process Had Been
Cancelled
The shutdown command sent through Liebert MultiLink or SNMP card
to the UPS is canceled,
ECO Mode Enabled
The UPS is configured to ECO mode operation,
ECO Mode Disabled
The UPS is configured to Online mode, supplying protected power to
the load through the inverter.
UPS Internal Temperature Return To
Normal
The internal temperature of the UPS recovers to normal range.
UPS Load Return From Overload
The loads are reduced, and the UPS recovers to normal state from
overload.
Load On Inverter
The inverter is on and supplies protected power to the load.
Load On ECO Bypass
The UPS is on ECO mode; the mains is supplying power to the load
directly to reduce energy usage.
Bypass Power Restored
The bypass power recovered and the UPS can now transfer to bypass.
Table 3-4
Warning list
Warning
Description
Mains Power Not Available
The mains power is not available, or it cannot satisfy the input
requirements for the UPS to operate from mains power
UPS Batteries Low And Exhausted Soon
The battery capacity is low and will be exhausted soon
UPS Has Switched To Battery Mode
The mains power is abnormal or the PFC side is faulty, the UPS
transfers back to Battery mode
Load On Bypass
The UPS transfers to Bypass mode, at this point, the input mains power
supplies power to the load directly, and the load is not protected
Input Power Wiring Error
L-N line reverse or PE not connected.
Bypass Power Not Available
The bypass power is not available, or it cannot satisfy the requirements
for the UPS transfers to bypass
UPS Maintenance Bypass Output
The UPS transfers to maintenance bypass.
AC input not qualified, cannot start UPS
The utility power is not qualified, the inverter cannot be powered up
Output disabled
REPO terminal connect error
Summary of Contents for Liebert GXT4-10000RT230
Page 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA User Manual ...
Page 2: ......
Page 44: ...Operation and Display Panel Liebert GXT4 User Manual 36 Page intentionally left blank ...
Page 52: ...Communication Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 60: ...Troubleshooting Liebert GXT4 User Manual 52 Page intentionally left blank ...
Page 67: ......